6-26
MHT260a (Engl.)
(13) Basic parameter 58
Para. Name Setting range Initial value Change
58 Overload early warning level 10 to 100% (in 1 step) 50 Always
* The trip level of amplifier is 100%.
The output level of overload early warning signal in control output signal can be set.
The overload (alarm detection) level of amplifier is 100%.
For details, see 5.6.6 Overload early warning.
(14) Basic parameter 59
Para. Name Setting range Initial value Change
59 Max. torque limit value 0 to max. torque [%] (in 1 step) 300 Always
* The rated torque is 100%.
The motor output torque can be limited by the para. setting value.
Where the torque limit (30) is not allocated.
The basic para. 59 is always effective.
Where the torque limit (30) is allocated.
Data can be changed between the max. torque and the basic para. 59 setting.
(15) Basic parameter 63, 64
Para. Name Setting range Initial value Change
63 Fixed point detection 1 1 to max. division number (in 1 step) 1 Always
64 Fixed point detection 2 1 to max. division number (in 1 step) 1 Always
The station number of fixed point 1 and fixed point 2 in control output signal can be set.