EasyManua.ls Logo

Fuji Electric FRENIC MEGA G2 Series - Page 115

Fuji Electric FRENIC MEGA G2 Series
970 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.4 Programming Mode
3-31
OPERATION USING THE KEYPAD
Chap 3
3.4.5 Reading maintenance information “Maintenance Information: 5.CHE
Menu number 5 “Maintenance Information: 5.CHE contains information necessary for performing maintenance on
the inverter. The menu transition in “Maintenance Information” is same as that in Menu #3 “Drive Monitoring.” (Refer
to Section 3.4.3 .)
The monitor number and symbol are displayed alternately every 1 second.
Basic key operation
(1) Turn the inverter ON. It automatically enters Running mode in which you press the key to switch to
Programming mode. The function selection menu appears.
(2) Use the and keys to display “Maintenance Information” (
5.CHE
).
Press the key to skip in menu number units.
(3) Press the key to proceed to the list of maintenance items (e.g.,
5_00
).
(4) Use the and keys to display the desired maintenance item, then press the key.
The data of the corresponding maintenance item appears.
Press the key to skip to maintenance information +10. When the end is reached, the display returns to
the first maintenance item.
(5) Press the key to return to the list of maintenance items. Press the key again to return to the menu.
Table 3.4-12 “Maintenance Information” display items
Monitor
No.
Symbol
Item
Displayed content
5_00
tiME
Cumulative run time
Displays the content of the cumulative power-ON time counter
of the inverter.
Counter range: 0 to 65,535 hours
When the count exceeds 65,535, the counter will be reset to
“0” and start over again.
5_01
Edc
DC link bus voltage
Displays the DC link bus voltage of the inverter main circuit.
Unit: V (volts)
5_02
ti.Max
Max. temperature
inside the inverter
Displays the maximum temperature inside the inverter for
every hour.
Unit: °C (Temperatures below 20 °C are displayed as 20 °C.)
5_03
tF.Max
Max. temperature of
heat sink
Displays the maximum temperature of the inverter heat sink
for every hour.
Unit: °C (Temperatures below 20 ºC are displayed as 20 ºC.)
5_04
i.MAx
Max. effective
output current
Displays the maximum current in RMS for every hour.
Unit: A (amperes)
5_05
CAP
Capacitance of the
DC link bus
capacitor
Displays the current capacitance of the DC link bus capacitor
(reservoir capacitor) in %, based on the capacitance when
shipping as 100%.
Refer to Chapter 7 MAINTENANCE AND INSPECTION for
details.
Display: %

Table of Contents

Related product manuals