12.1 Standard Specifications 1 (Basic Type)
12-1
SPECIFICATIONS
Chap 12
12.1 Standard Specifications 1 (Basic Type)
12.1.1 Three-phase 200V series
HHD specification for High, Heavy Duty applications
Item
Specification
Type (FRN***G2S-2G)
0003
0005
0008
0011
0018
0032
0046
0059
0075
0088
0115
0146
0180
0215
0288
0346
0432
Standard applicable motor
[kW (HP)] (*1)
(rated output)
0.4
(1/2)
0.75
(1)
1.5
(2)
2.2
(3)
3.7
(5)
5.5
(7.5)
7.5
(10)
11
(15)
15
(20)
18.5
(25)
22
(30)
30
(40)
37
(50)
45
(60)
55
(75)
75
(100)
90
(125)
Output ratings
Rated capacity [kVA]
(*2)
1.1
1.9
3.0
4.1
6.8
10
14
18
24
28
34
45
55
68
81
109
131
Rated voltage [V] (*3)
Three-phase 200 to 240 V (with AVR function)
Three-phase 200 to 230 V (with
AVR function)
Rated current [A]
3
5
8
11
18
27
37
49
63
76
90
119
146
180
215
288
346
Overload current
rating
150% for 1 min, 200% for 3.0 s
Input power supply
Voltage, frequency
Three-phase 200 to 240 V, 50/60 Hz
Three-phase 200 to 230 V,
50/60 Hz
Permissible voltage,
frequency fluctuation
Voltage: +10 to -15% (interphase unbalance ratio: 2% or less) (*4)
Frequency: +5 to -5%
Rated input
current [A]
(*8)
with
DCR
1.6
3.2
6.1
8.9
15.0
21.1
28.8
42.2
57.6
71.0
84.4
114
138
167
203
282
334
w/o
DCR
3.1
5.3
9.5
13.2
22.2
31.5
42.7
60.7
80.1
97.0
112
151
185
225
270
-
-
Required capacity
(with DCR) [kVA]
(*5)
0.6
1.2
2.2
3.1
5.2
7.4
10
15
20
25
30
40
48
58
71
98
116
Braking
Braking torque [%]
(*6)
150%
100%
20%
10 to 15%
Braking transistor
Built-in
-
Minimum connectable
resistance value [Ω]
100
40
24
16
12
8.0
6.0
4.0
2.5
2.25
2.0
1.6
-
Built-in braking
resistor [Ω]
100
40
20
-
Braking time [s]
5 s
-
Duty cycle [%ED]
5
3
5
3
2
3
2
-
DC reactor (DCR)
Option
Option
(*7)
Applicable safety
standards
UL61800-5-1, C22.2 No.274-17, IEC/EN 61800-5-1
Protective construction
(IEC 60529)
Enclosed IP20 type, UL open type
IP00, UL open type
IP55 at external side when
external cooling installed
Cooling system
Natural cooling
Fan cooling
Weight [kg (lbs)]
1.7
(3.6)
1.9
(4.2)
2.6
(5.7)
2.9
(6.3)
2.9
(6.4)
5.8
(13)
6.2
(14)
5.7
(13)
11
(23)
11
(24)
12
(25)
23
(51)
31
(68)
40
(88)
42
(93)
60
(132)
97
(214)
(*1) Fuji 4-pole standard motor
(*2) The rated capacity indicates 220 V for the 200V series, and 440 V for the 400V series.
(*3) It is not possible to output a voltage higher than the power supply voltage.
(*4) Interphase unbalance ratio (%) = Max. voltage [V] - min. voltage [V] / Three-phase average voltage [V] x 67
(See IEC/EN 61800-3)
If using the motor with an unbalance ratio of 2 to 3%, use an AC reactor (ACR: option).
(*5) This indicates the capacity when the motor is equipped with a DC reactor (DCR) (option).
(*6) This is the average braking torque value for the motor on its own. (This will vary based on the motor
efficiency.)