12.1 Standard Specifications 1 (Basic Type)
12.1 Standard Specifications 1 (Basic Type)
12.1.1 Three-phase 200V series
■ HHD specification for High, Heavy Duty applications
Standard applicable motor
[kW (HP)] (*1)
(rated output)
Rated capacity [kVA]
(*2)
Three-phase 200 to 240 V (with AVR function)
Three-phase 200 to 230 V (with
AVR function)
150% for 1 min, 200% for 3.0 s
Three-phase 200 to 240 V, 50/60 Hz
Three-phase 200 to 230 V,
50/60 Hz
Permissible voltage,
frequency fluctuation
Voltage: +10 to -15% (interphase unbalance ratio: 2% or less) (*4)
Frequency: +5 to -5%
Rated input
current [A]
(*8)
Required capacity
(with DCR) [kVA]
(*5)
Minimum connectable
resistance value [Ω]
Built-in braking
resistor [Ω]
Applicable safety
standards
UL61800-5-1, C22.2 No.274-17, IEC/EN 61800-5-1
Protective construction
(IEC 60529)
Enclosed IP20 type, UL open type
IP00, UL open type
IP55 at external side when
external cooling installed
(*1) Fuji 4-pole standard motor
(*2) The rated capacity indicates 220 V for the 200V series, and 440 V for the 400V series.
(*3) It is not possible to output a voltage higher than the power supply voltage.
(*4) Interphase unbalance ratio (%) = Max. voltage [V] - min. voltage [V] / Three-phase average voltage [V] x 67
(See IEC/EN 61800-3)
If using the motor with an unbalance ratio of 2 to 3%, use an AC reactor (ACR: option).
(*5) This indicates the capacity when the motor is equipped with a DC reactor (DCR) (option).
(*6) This is the average braking torque value for the motor on its own. (This will vary based on the motor
efficiency.)