5.3 Description of Function Codes 5.3.7 b, r codes (Speed control 3 and 4 parameters)
5-266
5.3.7 b, r codes (Speed control 3 and 4 parameters)
FRENIC-MEGA has four sets of speed control parameter. They can be selected by MPRM1, MPRM2signals.
The selection with speed control selection signals MPRM1and MPRM2takes priority over the selection made
with M2, M3, and M4.
For the description of speed control parameters, refer to function code d01.
Name
Speed control parameter set
Set 1
Set 2
Set 3
Set 4
Speed control (Speed command filter)
d01
A43
b43
r43
(Speed detection filter)
d02
A44
b44
r44
(P gain)
d03
A45
b45
r45
(Integral time)
d04
A46
b46
r46
(Feed forward gain)
d05
A47
b47
r47
(Output filter)
d06
A48
b48
r48
Select speed control parameter 1, 2 -- MPRM1, MPRM2(E01 to E05 data = 78, 79)
The combination of the ON/OFF states of digital input signals MPRM1and MPRM2selects one among 4 different
speed control parameter sets. d01 to d08 and A43 to A50 can be changed even when switching the motor with M2.
Input signal
Selected speed control parameter set
MPRM2
MPRM1
OFF
OFF
d01 to d06: Speed control constant 1
OFF
ON
A43 to A48: Speed control constant 2
ON
OFF
b43 to b48: Speed control constant 3
ON
ON
r43 to r48: Speed control constant 4