4.12 Selecting a Run Command Source
4-47
4.12 Selecting a Run Command Source
A run command source is the keypad ( and keys) by factory default.
4.12.1 Setting run commands from the keypad
Follow the procedure given below.
(1) Configure the function codes as listed below.
Table 4.12-1
0: Keypad operation
(Rotation direction input: terminal block)
2: Keypad operation (forward rotation)
3: Keypad operation (reverse rotation)
Please refer to Table 4.4-1
Initial value for each
destination
(2) When F02 = 0: Press the key on the keypad to run the motor. Press the key to stop the motor.
The rotation direction is specified with terminals [FWD] and [REV]. Connect the run forward switch between
terminals [FWD] and [CM] and the run reverse switch between [REV] and [CM].
(3) When F02 = 2: Press the key on the keypad to run the motor in the forward direction. Press the key
to stop the motor.
(4) When F02 = 3: Press the key on the keypad to run the motor in the reverse direction. Press the key
to stop it.
For details on how to modify the function code data, see Chapter 3 “3.4.1 Setting up function codes “Data
Setting””.
4.12.2 Setting run commands with external signals (terminal [FWD, [REV])
Follow the procedure given below.
(1) Configure the function codes as listed below.
Table 4.12-2
1: External digital input signal
Please refer to Table 4.4-1
Initial value for each
destination
If terminals [FWD] and [REV] are ON (short-circuited), the F02 setting cannot be changed. First turn
terminals [FWD] and [REV] OFF, and then change the setting.
(2) Connect the forward rotation command switch between terminals [FWD] and [CM], and connect the reverse
rotation command switch between terminals [REV] and [CM].
(3) By turning ON (short circuiting) the run command switches, operation is started.
For precautions in wiring, refer to Chapter 2 “INSTALLATION AND WIRING”.
For details on how to modify function code data, refer to Chapter 3 “3.4.1 Setting up function codes “Data
Setting””.