4.4 Destination setting
4-4
4.4 Destination setting
For inverter type FRN****G2■-G (Global Model), the destination must be set first after the initial power supply.
Without setting the destination, the function code cannot be changed. The inverter cannot be operated either. By
setting the destination, basic function codes such as rated voltage, rated frequency, etc. are initialized to general
values in each region (Table 4.4-1). If the destination value setting is changed after the initial destination setting, it
can be changed with 8.dest in the program mode menu or function code H101. If the destination is reset by
8.dest, all function codes are initialized to the factory defaults. If the destination is set by H101, only the
function codes in Table 4.4-1 are initialized to the values in Table 4.4-1. The destination can be selected from the
regions of Japan, Asia, China, Europe, Americas and Korea.
If the function code set including the destination setting function code (H101) is copied with the data copy function
or the FRENIC loader, manual destination setting is not required.
Set the initial destination as shown below.
(1) With 8.dest displayed, press key first.
(2)
asia (Asian region) is displayed first. For other regions, press key or key to select the destination.
(3) After selecting the destination, saUe is displayed by pressing key and the destination setting is
completed. Then, 0.00 is displayed.
Table 4.4-1 Initial value for each destination
F03/A01/b01/r01:Maximum output frequency 1 to 4
60.0Hz
(200V)
50.0Hz
(400V)
F04/A02/b02/r02:Base frequency 1 to 4
F05/A03/b03/r03:Rated voltage at base frequency 1 to 4
F06/A04/b04/r04:Maximum output voltage 1 to 4
F09/A05/b05/r05:Torque boost 1 to 4
Fuji IE3 motor Standard
value
Fuji IE3 motor Standard
value
F11/A07/b07/r07:Electronic thermal 1 to 4(Overload
detection level)
F14:Restart mode after momentary power failure (Mode
selection)
F80:Switching between HND and HHD drive modes
E31/E36/E54:Frequency detection 1 to 3(Level)
60.0Hz
(200V)
50.0Hz
(400V)
E34/E37/E55:Overload early warning/Current detection 1
to 3
Fuji IE3 motor Standard
value
Fuji IE3 motor Standard
value
P02/A16/b16/r16:Motor 1 to 4(Rated capacity)
P03/A17/b17/r17: Motor 1 to 4(Rated current)
Fuji IE3 motor Standard
value
Fuji IE3 motor Standard
value
P06/A20/b20/r20: Motor 1 to 4(No-load current)
P07/A21/b21/r21: Motor 1 to 4(%R1)
P08/A22/b22/r22: Motor 1 to 4(%X)
P12/A26/b26/r26: Motor 1 to 4(Rated slip frequency)
P55/A55/b55/r55: Motor 1 to 4(Torque current under vector
control)
P99/A39/b39/r39:Motor 1 to 4 selection
H96:STOP key priority/ Start check function
K01:Multifunction keypad TP-A2SW(Language selection)