10.4 Selecting the Inverter Rating Specification (HHD/HND)
10-16
10.4.2 Guideline for selecting inverter specification and capacity
Table 10.4-1 shows the functional differences between the HHD/HND specifications.
Provided that the application is satisfied with the HND specification in terms of both overload capability and
functionality, an inverter capacity (HND specification) one to two ranks lower than the capacity of the motor being
used can be selected.
Table 10.4-1 Functional differences between HHD/HND specifications
Function
HHD specification
HND specification
(FRN0032G2S-2G/FRN0018
G2-4G or above)
Remarks
Application
Heavy Duty applications
Normal Duty applications
-
Function code setting
value
(HHD/HND
specification
switching)
F80 data = 0
(factory default)
F80 data = 1
-
Continuous current
rating level
(inverter rated
current level)
Capable of driving a
motor whose capacity is
the same as the inverter
capacity.
Capable of driving a motor
whose capacity is one to
two ranks higher than the
inverter capacity.
In the case of the HND
specification, the continuous
current rating is one to two
ranks higher, but the
percentage (%) drops
relative to the continuous
current rating of the
overload capability. Refer to
“Chapter 12
“SPECIFICATIONS" for
details.
Overload capability
150% for 1 min,
200% for 3 s
120% for 1 min
DC braking
(braking level)
Setting range:
0 to 100%
Setting range:
0 to 80%
With the HND specification,
a value out of the range, if
specified, automatically
changes to the maximum
value allowable for the HND
specification.
Motor sound
(carrier frequency)
Setting range:
0.75 to 16 kHz
(FRN0003G2S-2G
to FRN0288G2S-2G)
(FRN0002G2-4G
to FRN0150G2-4G)
0.75 to 10 kHz
(FRN0346G2S-2G
to FRN0432G2S-2G)
(FRN0180G2-4G
to FRN1386G2-4G)
Setting range:
0.75 to 16 kHz
(FRN0032G2S-2G
to FRN0088G2S-2G)
(FRN0018G2-4G
to FRN0045G2-4G)
0.75 to 10 kHz
(FRN0115G2S-2G
to FRN0288G2S-2G)
(FRN0060G2-4G
to FRN0150G2-4G)
0.75 to 6 kHz
(FRN0346G2S-2G
to FRN0432G2S-2G)
(FRN0180G2-4G
to FRN1386G2-4G)
Current limiting level
Initial value: 180%
(FRN0075G2S-2G/
FRN0038G2-4G
or below)
Initial value: 160%
(FRN0088G2S-2G
/FRN0045G2-4G
or above)
Initial value: 130%
Switching the drive mode
with function code F80
automatically initializes the
F44 data to the value
specified at left.
Current indication
and output
Based on the rated
current level for HHD
specification inverter
Based on the rated current
level for HND specification
inverter
-