12.3 Common Specifications
12-12
12.3 Common Specifications
Table 12.3-1
5 to 599 Hz variable setting
5 to 599 Hz variable setting
(in conjunction with maximum output frequency)
Number of
motor poles
setting
0.1 to 60.0 Hz variable setting
(0.0 Hz when performing speed sensorless vector control/vector control
with speed sensor)
∙ 0.75 to 16 kHz variable setting
(HHD specification: FRN0003G2S-2G to FRN0288G2S-2G/
FRN0002G2■-4G to FRN0150G2■-4G)
(HND specification: FRN0032G2S-2G to FRN0088G2S-2G/
FRN0018G2■-4G to FRN0045G2■-4G)
∙ 0.75 to 10 kHz variable setting
(HHD specification: FRN0346G2S-2G to FRN0432G2S-2G/
FRN0180G2■-4G to FRN1386G2■-4G)
(HND specification: FRN0115G2S-2G to FRN0288G2S-2G/
FRN0060G2■-4G to FRN0150G2■-4G)
∙ 0.75 to 6 kHz variable setting
(HND specification: FRN0346G2S-2G to FRN0432G2S-2G/
FRN0180G2■-4G to FRN1386G2■-4G)
Note: The carrier frequency may automatically lower depending upon
the ambient temperature or the output current to protect the
inverter. (The automatic lowering function can be disabled.)
Output frequency
accuracy
∙ Analog setting: ±0.2% of maximum output frequency
(at 25 ±10 °C) (77 ±18 °F)
∙ Keypad setting: ±0.01% of maximum output frequency
(at -10 to +50 °C) (14 to 122 °F)
Frequency setting
resolution
∙ Analog setting: 1/3000 of maximum output frequency
∙ Keypad setting: 0.01 Hz
∙ Link setting: 1/20000 of maximum output frequency or 0.01 Hz (fixed)
When
performing V/f
control with
sensor (*1)
When
performing
dynamic torque
vector control
with sensor (*2)
∙ 1:20 (*1) (Minimum speed: Nominal speed)
∙ 1:200 (*2) (Minimum speed: Nominal speed)
∙ 1:2 (fixed torque area: fixed output area)
∙ Analog setting: ±0.2% of maximum output frequency or
below (at 25 ±10 °C) (77 ±18 °F)
∙ Digital setting: ±0.01% of maximum output frequency or
below (at -10 to +50 °C) (14 to 122 °F)