12.2 Standard Specifications 2 (Type with Built-in EMC Filter)
12-11
SPECIFICATIONS
Chap 12
Item
Specification
Type (FRN***G2E-4G)
0216
0260
0325
0377
0432
0520
0650
0740
0960
1040
1170
1386
Standard applicable
motor [kW (HP)] (*1)
(rated output)
110
(150)
132
(200)
160
(250)
200
(300)
220
(350)
280
(400)
355
(500)
400
(600)
500
(700)
560
(800)
630
(900)
710
(1000)
Output ratings
Rated capacity [kVA]
(*2)
164
198
247
287
329
396
495
563
731
792
891
1056
Rated voltage [V] (*3)
Three-phase 380 to 480 V (with AVR function)
Rated current [A]
216
260
325
377
432
520
650
740
960
1040
1170
1386
Overload current
rating
120% for 1 min
Input power supply
Voltage, frequency
Three-phase 380 to 480 V, 50/60 Hz
Permissible voltage,
frequency fluctuation
Voltage: +10 to -15% (interphase unbalance ratio: 2% or less) (*4)
Frequency: +5 to -5%
Rated input
current [A]
(*8)
with
DCR
201
238
286
357
390
500
628
705
881
990
1115
1256
Required capacity
(with DCR) [kVA] (*5)
140
165
199
248
271
347
436
489
611
686
773
871
Braking
Braking torque [%]
(*6)
7 to 12%
Braking transistor
-
Built-in braking
resistor
-
Braking time [s]
Duty cycle
[%ED]
-
EMC filter
Complying EMC standard on emissions and immunity: Category C3 (2nd Env.)
(IEC61800-3)
DC reactor (DCR)
Option (*7)
Applicable safety
standards
UL61800-5-1, C22.2 No.274-17, IEC/EN 61800-5-1
Protective construction
(IEC 60529)
IP00, UL open type
IP55 at external side when external cooling installed
Cooling system
Fan cooling
Weight [kg (lbs)]
60
(132)
60
(132)
89
(196)
89
(196)
116
(256)
124
(273)
221
(487)
221
(487)
291
(642)
295
(650)
450
(992)
450
(992)
(*1) Fuji 4-pole standard motor
(*2) The rated capacity indicates 220 V for the 200V series, and 440 V for the 400V series.
(*3) It is not possible to output a voltage higher than the power supply voltage.
(*4) Interphase unbalance ratio (%) = Max. voltage [V] - min. voltage [V] / Three-phase average voltage [V] x 67
(See IEC/EN 61800-3)
If using the motor with an unbalance ratio of 2 to 3%, use an AC reactor (ACR: option).
(*5) This indicates the capacity when the motor is equipped with a DC reactor (DCR) (option).
(*6) This is the average braking torque value for the motor on its own. (This will vary based on the motor
efficiency.)
(*7) If using motors with output of 75 kW or higher, be sure to use a DC reactor (option).
(*8) This specification is an estimated value to be applied when the power supply capacity is 500 kVA (Inverter
capacity × 10 when the capacity exceeds 50 kVA) and the power supply with %X = 5% is connected.