12.2 Standard Specifications 2 (Type with Built-in EMC Filter)
12-10
HND specification for High, Normal Duty applications
Item
Specification
Type (FRN***G2E-4G)
0018
0023
0031
0038
0045
0060
0075
0091
0112
0150
0180
Standard applicable motor
[kW (HP)] (*1)
(rated output)
7.5
(10)
11
(15)
15
(20)
18.5
(25)
22
(30)
30
(40)
37
(50)
45
(60)
55
(75)
75
(100)
90
(125)
Output ratings
Rated capacity [kVA] (*2)
13
17
23
28
34
45
57
69
85
114
137
Rated voltage [V] (*3)
Three-phase 380 to 480 V (with AVR function)
Rated current [A]
17.5
23
31
38
45
60
75
91
112
150
180
Overload current rating
120% for 1 min
Input power supply
Voltage, frequency
Three-phase 380 to 480 V, 50/60 Hz
Permissible voltage,
frequency fluctuation
Voltage: +10 to -15% (interphase unbalance ratio: 2% or less) (*4)
Frequency: +5 to -5%
Rated input
current [A] (*8)
with DCR
14.4
21.1
28.8
35.5
42.2
57
68.5
83.2
102
138
164
w/o DCR
23.2
33
43.8
52.3
60.6
77.9
94.3
114
140
-
-
Required capacity
(with DCR) [kVA] (*5)
10
15
20
25
30
40
48
58
71
96
114
Braking
Braking torque [%] (*6)
70%
15%
7 to 12%
Braking transistor
Built-in
Minimum connectable
resistance value [Ω]
64
48
32
24
16
10
9.0
8.0
6.5
4.7
Built-in braking resistor [Ω]
80
-
Braking time [s]
3.7 s
3.4 s
-
Duty cycle [%ED]
2.2
1.4
-
EMC filter
Complying EMC standard on emissions and immunity: Category C3 (2nd Env.)
(IEC61800-3)
DC reactor (DCR)
Option
Option (*7)
Applicable safety standards
UL61800-5-1, C22.2 No.274-17, IEC/EN 61800-5-1
Protective construction (IEC 60529)
Enclosed P20 type, UL open type
IP00, UL open type
IP55 at external side when external
cooling installed
Cooling system
Fan cooling
Weight [kg (lbs)]
6.6
(15)
6.6
(15)
6.4
(14)
11
(25)
11
(25)
12
(25)
23
(51)
23
(51)
30
(66)
31
(68)
38
(84)
(*1) Fuji 4-pole standard motor
(*2) The rated capacity indicates 220 V for the 200V series, and 440 V for the 400V series.
(*3) It is not possible to output a voltage higher than the power supply voltage.
(*4) Interphase unbalance ratio (%) = Max. voltage [V] - min. voltage [V] / Three-phase average voltage [V] x 67
(See IEC/EN 61800-3)
If using the motor with an unbalance ratio of 2 to 3%, use an AC reactor (ACR: option).
(*5) This indicates the capacity when the motor is equipped with a DC reactor (DCR) (option).
(*6) This is the average braking torque value for the motor on its own. (This will vary based on the motor
efficiency.)
(*7) If using motors with output of 75 kW or higher, be sure to use a DC reactor (option).
(*8) This specification is an estimated value to be applied when the power supply capacity is 500 kVA (Inverter
capacity × 10 when the capacity exceeds 50 kVA) and the power supply with %X = 5% is connected.