12.2 Standard Specifications 2 (Type with Built-in EMC Filter)
12-9
SPECIFICATIONS
Chap 12
Item
Specification
Type (FRN***G2E-4G)
0180
0216
0260
0325
0377
0432
0520
0650
0740
0960
1040
1170
1386
Standard applicable motor
[kW (HP)] (*1)
(rated output)
75
(100)
90
(125)
110
(150)
132
(200)
160
(250)
200
(300)
220
(350)
280
(400)
315
(450)
355
(500)
400
(600)
500
(800)
630
(900)
Output ratings
Rated capacity [kVA]
(*2)
114
137
164
198
247
287
329
396
445
495
563
731
891
Rated voltage [V (*3)
Three-phase 380 to 480 V (with AVR function)
Rated current [A]
150
180
216
260
325
377
432
520
585
650
740
960
1170
Overload current
rating
150% for 1 min, 200% for 3.0 s
Input power supply
Voltage, frequency
Three-phase 380 to 480 V, 50/60 Hz
Permissible voltage,
frequency fluctuation
Voltage: +10 to -15% (interphase unbalance ratio: 2% or less) (*4)
Frequency: +5 to -5%
Rated input
current [A]
(*8)
with
DCR
138
164
201
238
286
357
390
500
559
628
705
881
1115
Required capacity
(with DCR) [kVA] (*5)
96
114
140
165
199
248
271
347
388
436
489
611
773
Braking
Braking torque [%] (*6)
10 to 15%
Braking transistor
Build
in
-
Minimum connectable
resistance value [Ω]
4.7
-
Built-in braking
resistor
-
Braking time [s]
Duty cycle [%ED]
-
EMC filter
Complying EMC standard on emissions and immunity: Category C3 (2nd Env.)
(IEC61800-3)
DC reactor (DCR)
Option (*7)
Applicable safety standards
UL61800-5-1, C22.2 No.274-17, IEC/EN 61800-5-1
Protective construction
(IEC 60529)
IP00, UL open type
IP55 at external side when external cooling installed
Cooling system
Fan cooling
Weight [kg (lbs)]
38
(84)
60
(132)
60
(132)
89
(196)
89
(196)
116
(256)
124
(273)
221
(487)
221
(487)
291
(642)
295
(650)
450
(992)
450
(992)
(*1) Fuji 4-pole standard motor
(*2) The rated capacity indicates 220 V for the 200V series, and 440 V for the 400V series.
(*3) It is not possible to output a voltage higher than the power supply voltage.
(*4) Interphase unbalance ratio (%) = Max. voltage [V] - min. voltage [V] / Three-phase average voltage [V] x 67
(See IEC/EN 61800-3)
If using the motor with an unbalance ratio of 2 to 3%, use an AC reactor (ACR: option).
(*5) This indicates the capacity when the motor is equipped with a DC reactor (DCR).
(*6) This is the average braking torque value for the motor on its own. (This will vary based on the motor
efficiency.)
(*7) If using motors with output of 75 kW or higher, be sure to use a DC reactor (option).
(*8) This specification is an estimated value to be applied when the power supply capacity is 500 kVA (Inverter
capacity × 10 when the capacity exceeds 50 kVA) and the power supply with %X = 5% is connected.