5.3 Description of Function Codes 5.3.6 A, b, r codes (Motor 2 to 4 parameters)
5-261
FUNCTION CODES
Chap 5
FUNCTION
CODES
F Codes
E Codes
C Codes
P Codes
H Codes
A Codes
b Codes
r Codes
J Codes
d Codes
U Codes
y Codes
K Codes
5.3.6 A, b, r codes (Motor 2 to 4 parameters)
FRENIC-MEGA allows you to switch between 4 motors and perform operation using the same inverter. Furthermore,
operation can be performed by switching the control parameters and control method even for a single motor. These
changes are made using terminal commands M2, M3, and M4.
(Function codes E01 to E09, data = 12, 36, 37)
Function code
Motor to drive
Remarks
F/E/P codes, etc.
Motor 1
Including function codes commonly applied to motors 1 to 4.
A codes
Motor 2
b codes
Motor 3
r codes
Motor 4
The switching operation with M2, M3, and M4is made in order of priority from motor 1 to 4 using the following
combinations. By switching the motor, the respective function codes will change, and the motor will be controlled
based on the new function codes. SWM1, SWM2, SWM3, and SWM4can be output as digital signals used
to indicate the selected motor.
(Function codes E20 to E23 and E27, data = 48 to 51)
Digital input signal
Selected motor
Output signal
M2
M3
M4
SWM1
SWM2
SWM3
SWM4
OFF
OFF
OFF
Motor 1
ON
OFF
OFF
OFF
ON
-
-
Motor 2 (A codes)
OFF
ON
OFF
OFF
OFF
ON
-
Motor 3 (b codes)
OFF
OFF
ON
OFF
OFF
OFF
ON
Motor 4 (r codes)
OFF
OFF
OFF
ON
Induction motor control only. This manual describes function codes applied to motor 1 only. For ones
applied to motors 2 to 4, refer to the corresponding function codes for motor 1 in Table 5.3-21.
Synchronous motor control is possible only for motor 1. If changes are not made to the inverter output
wiring when switching to induction motor control for motors 2 to 4, synchronous motors will be driven by
induction motors, possibly leading to motor damage, and therefore caution is advised.
It is necessary to confirm M2, M3, and M4within 1 ms of the run command being confirmed.