• Carry out inspection after waiting 5 minutes or longer for units of FRN0115G2S-2G/FRN0060G2□-4G or
lower, or 10 minutes or longer for units of FRN0146G2S-2G/FRN0075G2□-4G or higher after turning OFF
the power. Furthermore, ensure that the LED monitor and charge lamp are OFF, and use a device such as a
tester to ensure that the DC intermediate circuit voltage across main circuit terminals P(+) and N(-) has
dropped to a safe level (+25 VDC or less).
Failure to observe this could result in electric shock.
• Be sure to perform the daily inspection and periodic inspection described in the instruction manual. Lengthy
use of the product without inspection could result in inverter failure and damage, or accident and fire.
• A periodic inspection cycle of 1 to 2 years is recommended, however, the cycle may be shortened
depending on the usage conditions.
• It is recommended that parts for periodic replacement be replaced after the standard number of years
indicated in the instruction manual. Lengthy use of the product without replacing parts could result in inverter
failure and damage, or accident and fire.
• Contact outputs [30A/B/C] and [Y5A/C] use relays, and may remain ON or OFF, or in an indefinite state
when the life is reached. In the interests of safety, equip the product with an external protection function.
Failure to observe this could result in fire or an accident.
• Maintenance and inspection, and part replacement should only be carried out by the authorized personnel.
• Remove all metal objects (watches, rings, etc.) before beginning work.
• Be sure to use insulated tools.
• Never modify the product.
Failure to observe this could result in electric shock or injury.
The drawings in this User's Manual are used to provide detailed descriptions, and therefore some may be
drawn with covers or safety shields removed. When running the product, do so only after returning covers or
shields to their prescribed original locations, and then run as described in the User's Manual.