5.3 Description of Function Codes 5.3.1 F codes (Fundamental functions)
Braking timer at the startup (H195)
When starting up inverter by run command, it is possible to start by operating DC braking.
This is particularly useful in applications such as hoists and elevators where the inverter runs at low speed braking
mode after starting up, preventing loads from falling.
• Data setting range: 0.00: No DC braking at the start up 0.01 to 30.00 (s)