5.3 Description of Function Codes 5.3.2 E codes (Extension terminal functions)
No function assigned “NONE” assignment (Function code data = 100)
It allows the inverter to run unaffected by ON/OFF of signals. It is used when a signal is externally input using
customizable logic. It is also used to temporarily disable a terminal function.
Light load automatic double speed judgment permission “LAC-ENB” assignment (Function code data
= 105)
This is used with the hoist function. Refer to the hoist function explanation for details.
( Function code d170)
Servo lock gain selection “SLG2” assignment (Function code data = 110)
By turning “SLG2” ON, servo lock gain is changed to servo lock gain 2. Switching is possible during operation.
( Function codes J97, d28)
Forced stop (for control terminals) “STOP-T” assignment (Function code data = 111)
Turning this terminal command “STOP-T” OFF causes the motor to decelerate to a stop in accordance with the H56
data (Deceleration time for forced stop). After the motor stops, the inverter enters the alarm state with the alarm
er6 displayed. This provides the same function as “STOP”, but is a dedicated signal for control terminals (actual
terminals), and does not function with communication commands.
( Function code F07)
AVR cancel “AVR-CCL” assignment (Function code data = 116)
Based on F05 setting value
Disable (same operation as F05 = 0)
Speed regulator P selection “P-SEL” assignment (Function code data = 119)
This is a P selection signal used with position control.
Refer to function codes d201 to d299 for details on position control.
Customizable logic input signal 1 to 9 “CLI1” to “CLO9” assignment (Function code data = 121 to 129)
It allows the inverter to run unaffected by ON/OFF of signals. It is used when a signal is externally input using
customizable logic.
( Function code U00)
Forced operation “FMS” assignment (Function code data = 134)
By turning “FMS” ON, almost all inverter protective operations are disabled, and inverter output continues until a
fault occurs. This is used when not wishing to trip inverters in such cases as when using with emergency exhaust
equipment.
( Function codes H116 to H121)
Position control related function “INC/ABS” assignment (Function code data = 135 to 147)
This signal is used with position control.
Refer to function codes d201 to d299 for details on position control.