5.3 Description of Function Codes 5.3.3 C codes (Control functions)
5-198
Gain and bias
Terminal
PID command, feedback, analog monitor
[12]
[C1] (C1 function)
[V2]
[C1] (V3 function)
These are biases and bias reference points used for PID command, PID feedback, frequency command 2 and
analog monitor. For details, refer to the description of F01 and J01.
Bias (C55, C61, C67, C82, o66, o82)
Data setting range: -200.00 to 200.00(%)
Bias reference point (C56, C62, C68, C83)
Data setting range: 0.00 to 100.00(%)
Specifying the bias as a negative value allows an input to be specified as bipolar for a unipolar analog input. By
setting C40 data to 10 or 11 for terminal [C1] (C1 function), the input value takes negative polarity with an analog
input of 0 point or lower.
Reference frequency
Analog input
Point A
Gain
Point B
Bias
Bias base
point
Gain base
point
Reference frequency
Gain
Bias
Bias base
point
Gain base
point
Point A
Point B
Analog input
Reference frequency
Analog input
Point A
Point B
Gain
Bias
Bias base
point
Gain base
point
(C75)
(C77)
(C83)
(C82)
Reference frequency
Gain
Bias
Analog input
Bias base
point
Gain base
point
Point A
Point B