5.3 Description of Function Codes 5.3.3 C codes (Control functions)
5-200
C59, C60
C65, C66
C71, C72
C85, C86
Analog input adjustment (terminal [12]) (Maximum scale, Minimum scale)
Analog input adjustment (terminal [C1] (C1 function)) (Maximum scale, Minimum scale)
Analog input adjustment (terminal [V2]) (Maximum scale, Minimum scale)
Analog input adjustment (terminal [C1] (V3 function)) (Maximum scale, Minimum scale)
Values of the analog input monitor (terminals [12], [V2], and [C1] (C1 and V3 functions) can be converted into easily
recognizable physical quantities for display. This function can also be used for PID feedback and PID command
values.
Data setting range: (maximum scale and minimum scale) -999.00 to 0.00 to 9990.00
C89
C90
Frequency compensation 1 with communication (Numerator)
Frequency compensation 2 with communication (Denominator)
A compensation value can be set for frequency settings via RS-485 communication or field bus communication.
This is used if wishing manually compensate the frequency determined by the system. By displaying these function
codes with the keypad, values are displayed in hexadecimal format. If data 0 is set, it is handled as 1.
Data setting range: -32768 to 32767 (keypad display: h.8000 to h.7FFF)
Last frequency setting = Frequency setting with communication x
C89: Frequency compensation 1 (numerator)
C90: Frequency compensation 2 (denominator)
C94 to C96
Jump frequency 4 to 6 (Refer to C01)
A detailed explanation can be found in the function code C01.
C99
Digital setting frequency (Refer to F01)
Displays the digital setting frequency set with the frequency setting using the keypad that becomes valid when F01
= 0. Changes to C09 can only be made with communication. C99 is copied using the keypad or PC Loader copy
function, allowing the digital setting frequency to be copied.
Maximum scale
(C59)
Minimum scale
(C60)
Indicated value
Analog input
(terminal [12])