5.3 Description of Function Codes 5.3.4 P codes (Motor 1 parameters)
5-208
P40, P41
For manufacturer
These function codes are reserved for particular manufacturers. Unless otherwise specified, do not access these
function codes.
P53, P54
Motor 1 (%X correction factor 1, 2)
This is a factor for correcting leakage reactance %X. Basically, there is no need to modify the setting.
P55
Motor 1 (Torque current under vector control)
Sets the torque current rated value under vector control with speed sensor.
The combination of P99 (Motor 1 selection) and P02 (Motor 1 rated capacity) data determines the standard value.
To change the standard value, do so after specifying these settings.
Basically, there is no need to modify the setting.
P56
Motor 1 (Induced voltage factor under vector control)
Sets the induced voltage under vector control with speed sensor.
The combination of P99 (Motor 1 selection) and P02 (Motor 1 rated capacity) data determines the standard value.
To change the standard value, do so after specifying these settings.
Basically, there is no need to modify the setting.
P57
Motor 1 (Reserved)
This is displayed, but is reserved for particular manufacturers. Unless otherwise specified, do not access these
function codes.
P60 to P64
Motor 1 (Synchronous motor armature resistance, d-axis inductance, q-axis
inductance, Induced voltage, Iron loss)
P60 through P64 specify the armature resistance, d-axis inductance, q-axis inductance, induced voltage and iron
loss of the motor, respectively. Obtain the appropriate values from the test report of the motor or by calling the
manufacturer of the motor. Furthermore, P60 to P63 are set automatically by performing auto tuning.
P65, P85
Motor 1 (Synchronous motors q-axis inductance magnetic saturation correction, Flux
limitation value)
These are the control parameter for PMSMs. Normally, it is not necessary to change the data of these function
codes.
P74
Motor 1 (Synchronous motors - Reference current when starting)
When the motor starts, the set starting current flows in the area at or below the output frequency level set at P89,
the magnetic pole position is drawn in, and operation is performed. Increase the setting value if the torque is
insufficient.