5.3 Description of Function Codes 5.3.8 J codes (Applied functions) 
 
 
  D differential time (J05) 
J05 specifies the differential time for the PID processor. 
•  Data setting range: 0.00 to 600.00 (s) 
0.00 indicates that the differential component is ineffective. 
D (Differential) action 
An operation in which the MV (manipulated value: output frequency) is proportional to the differential value of the 
deviation is called D action, which outputs the  MV that  differentiates the  deviation. D  action makes the inverter 
quickly respond to a rapid change of deviation. 
The  effectiveness  of  D  action  is  expressed  by  differential  time  as  parameter,  that  is  J05  data.  Setting  a  long 
differential time will quickly suppress oscillation caused by P action when a deviation occurs. Too long differential 
time makes the inverter output oscillation more. Setting short differential time will weakens the suppression effect 
when the deviation occurs. 
 
 
 
The combined uses of P, I, and D actions are described below. 
(1)  PI control 
PI control, which is a combination of P and I actions, is generally used to minimize the remaining deviation caused 
by  P  action.  PI  control  always  acts  to  minimize  the  deviation  even  if  a  commanded  value  changes  or  external 
disturbance steadily occurs. However, the longer the integral time of I action, the slower the system response to 
quick-changed control. P action can be used alone for loads with very large part of integral components. 
(2)  PD control 
In PD control, the moment that a deviation occurs, the control rapidly generates greater MV (manipulated value: 
output frequency) than that generated by D action alone, to suppress the deviation increase. When the deviation 
becomes small, the behavior of P action becomes small. A load including the integral component in the controlled 
system may oscillate due to the action of the integral component if P action alone is applied. In such a case, use 
PD control to reduce the oscillation caused by P action, for keeping the system stable. That is, PD control is applied 
to a system that does not contain any damping actions in its process. 
(3)  PID control 
PID control is  implemented by  combining P action with  the deviation  suppression of  I action  and the oscillation 
suppression of D action. PID control features minimal control deviation, high precision and high stability. In particular, 
PID control is effective to a system that has a long response time to the occurrence of deviation. 
Follow the procedure below to set data to PID control function codes. 
It is highly recommended that you adjust the PID control value while monitoring the system response waveform of 
the  PID  feedback  with  an  oscilloscope  or  equivalent.  Repeat  the  following  procedure  to  determine  the  optimal 
solution for each system. 
•  Increase the data of J03 (PID control P (Gain)) within the range where the feedback signal does not oscillate. 
•  Decrease the data of J04 (PID control I (Integral time)) within the range where the feedback signal does not 
oscillate. 
•  Increase the data of J05 (PID control D (Differential time)) within the range where the feedback signal does not 
oscillate.