5.3 Description of Function Codes 5.3.9 d codes (Applied functions 2)
Light load automatic double speed operation function
This function increases the speed to improve work efficiency when the load is light.
By turning ON digital input “LAC-ENB”, automatically double speed operation is enabled. By setting a light load
detection level and heavy load detection level, loads are distinguished in 3 levels (light load < medium load < heavy
load), and with light and medium loads, the motor runs at higher than the set frequency at the double speed rate.
Digital output “LAC” indicating that the motor is running at double speed turns ON at this time. However, double
speed operation is not performed if the set frequency is equal to or higher than the base frequency. With heavy
loads, the motor runs at the set frequency. By setting 999 for the double speed rate, the speed at which the motor
runs is automatically calculated from the load and a safety factor. In the interests of safety, adjustment of the load
detection function gain and offset (d171 to d174) must be complete to use this function.
ON
X Y
ON
FWD
REV
DILAC-ENB
Z
||
Y
F08
Y
F04
X
X
0
0
OFF
OFF OFF
d179:
d180:
Z
Z
E30:
d179:
d180:
ON
DOLAC
OFF
OFF
ON
OFF OFF
[%]
[%]
Function code
Terminal [X1] to [X9] (Function selection)
Terminal [FWD] (Function selection)
Terminal [REV] (Function selection)
105 (1105): Light load automatic double
speed judgment permission “LAC-ENB”
Terminal [Y1] to [Y4] (Function selection)
Terminal [Y5A/C] (Function selection)
Terminal [30A/B/C] (Function selection)
159 (1159): Performing light load automatic
double speed operation “LAC”
Light load speed multiplying factor
(hoisting)
100.0 to 300.0%, 999 (automatic)
Light load speed multiplying factor
(lowering)
100.0 to 300.0%, 999 (automatic)
Medium load speed multiplying factor
(hoisting)
100.0 to 300.0%, 999 (automatic)
Medium load speed multiplying factor
(lowering)
100.0 to 300.0%, 999 (automatic)
Speed multiplying factor safety factor
Load judgment delay time (hoisting)
Load judgment delay time (lowering)
Light load detection level (hoisting)
5.0 to 100.0%, 999 (disable)
Light load detection level (lowering)
5.0 to 100.0%, 999 (disable)
Heavy load detection level (hoisting)
5.0 to 100.0%, 999 (disable)
Heavy load detection level (lowering)
5.0 to 100.0%, 999 (disable)
Light load automatic
double speed enabled
DI signal “LAC-ENB”
Performing light load automatic
double speed operation
DO signal “LAC”
Double speed judgment delay time
d179: Hoisting
d180: Lowering
Double speed
frequency setting
Automatically calculated from
frequency setting Y x multiplying factor setting value,
or from load [%]
E30: Frequency arrival
detection width
Automatically calculated from
frequency setting Z x
multiplying factor setting value,
or from load [%]
Double speed
frequency setting
Double speed judgment delay time
d179: Hoisting
d180: Lowering