5.3 Description of Function Codes 5.3.9 d codes (Applied functions 2)
5-348
Overload stop function
Load judgment is performed when the judgment delay time after reaching speed (d186) is passed when hoisting
(FWD), and operation is stopped due to an overload if the overload detection level (d187) is exceeded. It is
recommended that judgment be based on the low speed frequency to ensure that overloads can be detected when
hoisting grounded loads.
Digital output “LLIM” is turned ON at the same time as the overload is detected, and e-ldis displayed on the
keypad. If lowering (REV) is possible, and the REV command is turned OFF after the load has been lowered to the
floor, “LLIM” turns OFF, and e-ld” disappears. In the interests of safety, adjustment of the load detection function
gain and offset (d171 to d174) must be complete to use this function.
E30:󰻝󰧹󲏊󰲉󰔽
OFF
OFF

󰔔󰢇
REV
󰲉󱱕󲒽
󰻝󰧹󰢇
󰷀󰨠
󰲉󱱕󲒽
󲏄󱱕󲒽󰎤󲎽󰖰󰪍󲚌
d186
OFF
󲏄󱱕󲒽󰲉
LLIM
ON
ON
ON
󰔔󰢇
FWD
󰾗󲎠󰪍󲚌󲁠󰎤󰘲󰾗󲎠
󰔔󱘸󰷧
ON
OFF
OFF
ON
OFF
F39󲷙󰷧󰻝
󰧹󱣦󱣧󰪍󲚌
F24󲷙󰊿󰻝
󰧹󱣦󱣧󰪍󲚌
d188:󲏄󱱕󲒽󰲉󱱕󲒽
󰏴󱍾
󰔔
0
OFF
OFF
OFF
=OFF
LLIM=OFF
󲏄󱱕󲒽󰲉
d187
0
0
󲏄󱱕󲒽󰎤
󰬨󲚌,󱽓󱘈 E-Ld
󱽓󱘈
Function code
Function
code
Name
Data setting range
Factory
default
Change
during
operation
E20 to
E24,
E27
Terminal [Y1] to [Y4] (Function selection)
Terminal [Y5A/C] (Function selection)
Terminal [30A/B/C] (Function selection)
158 (1158): Overload detection signal “LLIM”
-
N
d186
Overload judgment delay time
0.00 to 10.00 s
0.50
Y
d187
Overload detection level
1.0 to 250.0%, 999 (disable)
999
Y
d188
Overload detection monitor
Dedicated monitor function code: -327.68 to
+327.67%
-
-
Overload detection “LLIM” assignment (Function code data = 158)
By assigning this signal to a digital output, the inverter is able to monitor that an overload has been detected. The
signal turns ON when an overload is detected, the REV command is turned ON to lower the load, and when lowering
stops (REV = OFF), this signal also turns OFF.
Overload
judgment
Decelerate based on
deceleration time setting
Hoisting
prohibited
F24: Starting frequency
E30: Frequency arrival detection width
Frequency command
Inverter output
Hoisting command
FWD”
Lowering command
REV”
Detected load
Overload detection level
d187
Detected load held
until next judgment
LLIM” = OFF
when inverter output = OFF
Keypad display alternates between “E-Ld” and
monitor value during this time
Overload judgment delay time
d186
d188: Overload detection load
[For monitoring]
Performing overload detection
LLIM”
(Holding time)
F39: Stop frequency
(holding time)
Lowering
possible