11.10 Compact Power Regeneration PWM Converter
11-50
[ 3 ] Terminal functions
Connect to a three-phase power supply via a dedicated reactor.
Connect to inverter power supply input terminals P and N.
Control power auxiliary input
These are backup terminals for the control power. (30 kW or higher)
This is a terminal for grounding.
Synchronous power supply input
for voltage detection
This is a voltage detection terminal used for control inside the converter,
and is connected to the dedicated filter power supply side.
Charging circuit control output
This is the control output for the external charging circuit.
Contact capacity: 250 VAC, 5 A
Runs when ON across RUN and CM, and stops when OFF.
By eliminating the cause of the alarm when an alarm stoppage occurs, and
turning ON between RST and CM, the protective function that was
activated is canceled, and operation resumes.
Digital input
(SINK / SOURCE)
Signals selected from the following functions can be input.
0: External alarm [THR], 1: Current limiting cancel [LMT-CCL],
2: 73 answerback [73ANS], 3: Current limiting switch [I-LIM],
14: Universal DI [U-DI], 15: AC fuse blown [ACF]
Connects the power supply for PLC output signals. The terminal can also
be used as the power supply for loads connected to transistor outputs.
Rated voltage: +24 V (22 to 27 VDC), max. output current: 100 mA
This is a common terminal for digital input signals.
Total alarm output
(non-voltage contact signal (1C)
output)
A signal is output when the protective function activates and an alarm
stoppage occurs.
Contact capacity: 250 VAC, 0.3 A, cosφ = 0.3
Signals selected from the following functions can be output.
0: Running [RUN], 1: Ready for operation [RDY], 2: Power supply current
limiting [IL], 3: Lifetime early warning [LIFE], 4: Cooling fin overheating
early warning [PRE-OH], 5: Overload early warning [PRE-OL], 6: Power
running [DRV], 7: Regenerating [REG],
8: Current limiting warning [CUR], 9: Restart after momentary power failure
[U-RES], 10: Source frequency synchronization [SY-HZ], 11: Alarm
information [AL1], 12: Alarm information [AL2], 13: Alarm information [AL4],
14: DC fan lock [DCFL], 25: Universal DO [U-DO],
27: Cooling fan running [FAN], 32: Alarm output (for any alarm) [ALM], 33:
Y-terminal test output ON [Y-ON], 34: Y-terminal test output OFF [Y-OFF]
This is a common terminal for transistor output signals.
Signals can be selected in the same way as terminals Y1 to Y3.
Contact capacity: 250 VAC, 0.3 A, cosφ = 0.3
The following monitor signals are output by selecting from analog DC
voltage 0 to 10 V, DC current 4 to 20 mA, or in pulse 25 to 32000 p/s.
(FM2 can output DC voltage only).
0: Power supply side power [PWR] 200%/+10 V,
1: Power supply side current RMS value [I-AC] 200%/+10 V,
2: Power supply side voltage RMS [V-AC] 250 (500) V/10 V,
3: Intermediate DC voltage [V-DC] 500 (1000) V/10 V,
4: Power supply frequency [FREQ] 100 Hz/10 V,
5: +10 V output test [P10]
This is a common terminal for analog output signals.
For keypad connection
RJ-45 connector
This is used to connect the keypad. The keypad power is supplied from the
converter via an extension cable for remote operation.
RS-485 communication port
This is used to connect a computer or programmable controller, etc. by RS-
485 communication.