11.11 DC Reactors (DCRs)
11-64
(Note 1) □ is replaced by a letter of the alphabet indicating the inverter type.
□
S (basic type), E (type with built-in EMC filter)
(Note 2) Generated losses listed in the above tables are approximate values that are calculated according to the
following conditions:
• The power supply is 200 V or 400 V 50 Hz with 0% interphase voltage unbalance ratio.
• The capacity of the power supply used is the larger of either 500 kVA or 10 times the rated capacity of
the inverter.
• The motor is a 4-pole standard model at full load (100%).
• An AC reactor (ACR) is not connected.
(Note 3) Power factor based on differences in reactor type (at rated output)
DCR2/4-□□/□□A/□□B input power factor: approx. 90 to 95%
DCR2/4-□□C input power factor: approx. 86 to 90%
The standard applicable motor lineup also includes a DCR2/4-□□B type for 75 kW or higher models.
Please contact Fuji Electric for details.