12.1 Standard Specifications 1 (Basic Type)
12-3
SPECIFICATIONS
Chap 12
HND specification for High, Normal Duty applications
Item
Specification
Type (FRN***G2S-2G)
0032
0046
0059
0075
0088
0115
0146
0180
0215
0288
0346
0432
Standard applicable motor
[kW(HP)] (*1)
(rated output)
7.5
(10)
11
(15)
15
(20)
18.5
(25)
22
(30)
30
(40)
37
(50)
45
(60)
55
(75)
75
(100)
90
(125)
110
(150)
Output ratings
Rated capacity [kVA] (*2)
12
17
22
28
33
43
55
68
81
109
131
164
Rated voltage [V] (*3)
Three-phase 200 to 240 V (with AVR
function)
Three-phase 200 to 230 V (with AVR
function)
Rated current [A]
31.8
46.2
59.4
74.8
88
115
146
180
215
288
346
432
Overload current rating
120% for 1 min
Input power supply
Voltage, frequency
Three-phase 200 to 240 V, 50/60 Hz
Three-phase 200 to 230 V,
50/60 Hz
Permissible voltage,
frequency fluctuation
Voltage: +10 to -15% (interphase unbalance ratio: 2% or less) (*4)
Frequency: +5 to -5%
Rated input current
[A] (*8)
with
DCR
28.8
42.2
57.6
71
84.4
114
138
167
203
282
334
410
w/o
DCR
42.7
60.7
80.1
97
112
151
185
225
270
-
-
-
Required capacity
(with DCR) [kVA] (*5)
10
15
20
25
30
40
48
58
71
98
116
143
Braking
Braking torque [%] (*6)
70%
15%
7 to 12%
Braking transistor
Built-in
-
Minimum connectable
resistance value [Ω]
16
12
8.0
6.0
4.0
2.5
2.25
2.0
1.6
Built-in braking resistor [Ω]
20
-
Braking time [s]
3.7 s
3.4 s
Duty cycle [%ED]
2.2
1.4
-
DC reactor (DCR)
Option
Option (*7)
Applicable safety standards
UL61800-5-1, C22.2 No.274-17, IEC/EN 61800-5-1
Protective construction (IEC
60529)
Enclosed IP20 type, UL open type
IP00, UL open type
IP55 at external side when external cooling
installed
Cooling system
Fan cooling
Weight [kg (lbs)]
5.8
(13)
6.2
(14)
5.7
(13)
11
(23)
11
(24)
12
(25)
23
(51)
31
(68)
40
(88)
42
(93)
60
(132)
97
(214)
(*1) Fuji 4-pole standard motor
(*2) The rated capacity indicates 220 V for the 200V series, and 440 V for the 400V series.
(*3) It is not possible to output a voltage higher than the power supply voltage.
(*4) Interphase unbalance ratio (%) = Max. voltage [V] - min. voltage [V] / Three-phase average voltage [V] x 67
(See IEC/EN 61800-3)
If using the motor with an unbalance ratio of 2 to 3%, use an AC reactor (ACR: option).
(*5) This indicates the capacity when the motor is equipped with a DC reactor (DCR) (option).
(*6) This is the average braking torque value for the motor on its own. (This will vary based on the motor
efficiency.)
(*7) If using motors with output of 75 kW or higher, be sure to use a DC reactor (option).
(*8) This specification is an estimated value to be applied when the power supply capacity is 500 kVA (Inverter
capacity × 10 when the capacity exceeds 50 kVA) and the power supply with %X = 5% is connected.