12.3 Common Specifications
Inverse operation: Can be switched from “0 to +10 VDC/0 to 100%” to
“-10 to 0 VDC/0 to 100%” from an external source.
Can be switched from “4 to 20 mA DC/0 to 100%” to
“20 to 4 mA DC/0 to 100%” from an external source.
Can be switched from “0 to 20 mA DC/0 to 100%” to
“20 to 0 mA DC/0 to 100%” from an external source.
Pulse train input :
(standard)
Pulse input = terminal [X6], [X7],
forward/reverse pulse, pulse + rotation direction
Complementary output: Max. 100 kHz
Open collector output: Max. 30 kHz
Pulse train input :
(option)
PG interface option, forward/reverse pulse,
pulse + rotation direction
Complementary output: Max. 100 kHz
Open collector output: Max. 30 kHz
Acceleration/deceler
ation time
Setting range: Setting range from 0.00 to 6000 s
Switching: The four types of acceleration/deceleration time can be set or
selected individually (switchable during operation).
Acceleration/deceleration pattern:
Linear acceleration/Deceleration, S-curve acceleration/deceleration
(week, random (weak)), curve line acceleration/deceleration (max.
acceleration/deceleration at rated output)
Deceleration mode (coast to stop):
Shutoff of the run command lets the motor coast to a stop.
Forcible stop deceleration time:
Deceleration stop in exclusive deceleration time by forced stop
(STOP).
JOG dedicated acceleration/deceleration time
Acceleration/deceleration time is changed to 0 with
acceleration/deceleration operation cancel "BPS".