-100-
(ESC, , , ENT)
Zero adjustment: Set zero/Clear available
Damping: 0 to 100s (every 0.1s) for analog output
Low rate cutoff:
Alarm: Digital output available for Hardware
fault or Process fault
Burnout: Analog output: Hold/Overscale/Under-
scale/Zero selectable
Flow rate total: Hold/Count selectable
Burnout timer: 10 to 900s (every 1s)
Bi-directional range:
independently.
Hysteresis: 0 to 10% of working range
Working range applicable to digital output
Auto-2 range:
-
dently
Hysteresis: 0 to 10% of working range
Working range applicable to digital output
Flow switch:
independently
Digital output available for status at actu-
ated point
Total switch:
Digital output available when actuated
External total preset:
Preset total settable upon contact input
setting
Backup of power failure:
backup by non-volatile memory
Physical
Type of enclosure:
Flow transmitter: FSV···S: IP66
FSV···H: IP67 (With
large LCD)
Mounting method:
Flow transmitter: Mounted on wall or by
2B pipe
Detector: Clamped on pipe surface
External terminal of
transmitter:
plug terminal
PC Loader software
Provided as standard
•Compatible model is PC/AT compatible instrument.
•Main functions: Software for Main unit parameter setting/
change on PC
•OS: Windows 2000/XP or Windows 7 (Home Premium,
Professional)
•Memory requirement: 125MB min.
•Disk unit: CD-ROM drive compatible with Windows 2000/
XP or Windows 7 (Home Premium, Professional)
•Hard disk capacity: Minimum vacant capacity of 52MB
or more
Note:
th
digit of code symbols).
Note: Communication converter
For tne PC that supports RS-232C serial interface,
RS-232C - RS-485 converter is needed for connecting
the PC and main unit.
For the PC that does not support RS-232C serial
interface, additionally, USB - RS232C converter is
also needed.
<Recommendation>
[RS-232C - RS-485 converter]
RC-770X(manufactured by SYSMEX RA)
[USB - RS-232C converter]
USB-CVRS9 (manufactured by SANWA SUPPLY)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fuji Electric Time Delta-C FSV-2 and is the answer not in the manual?

Fuji Electric Time Delta-C FSV-2 Specifications

General IconGeneral
BrandFuji Electric
ModelTime Delta-C FSV-2
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals