-65-
4.11.2. How to set the constant current output
Description
Generates a fixed value output of analog signal.
Application example: The operation of a connected receiver is checked by generating a fixed value output of analog signal.
n the constant current setting mode (OUTPUT SETTING), set the constant current output value.
Settable range: -20%(0.8mA) to +120%(23.2mA)
For actual keying, refer to the typical operation indicated below. Set the protection to OFF beforehand. (See Section 4.4.1.)
Operation
(example)
Set the constant current output of 50% (12mA).
Key operation Description Display
Press the key for 4 times to display “MAINTENANCE MODE”.
MAINTENANCE MODE
ENT
Press the
ENT
key once to display “RAS INFORMATION”.
RAS INFORMATION
0000000000000000
Press the key twice to display “OUTPUT SETTING”.
CURRENT
OUTPUT SETTING
ENT
Press the
ENT
key once to display the setting screen.
OUTPUT SETTING
0 %
ENT
Press the
ENT
key once to blink the cursor.
Note) Start constant current output.
OUTPUT SETTING
+000 %
Enter “5” by the and the key.
OUTPUT SETTING
+050 %
ENT
Press the
ENT
key once to output 12mA.
OUTPUT SETTING

COMPLETE

――― Outputting 12mA. ――
OUTPUT SETTING
50 %
ESC
Press the
ESC
key once to stop constant current output.
Note) Current output is in the measurement status.
CURRENT
OUTPUT SETTING
ESC
Press the
ESC
key once and then press the key once to enter the
measurement mode.
0.000 %
0.000 m3