-59-
4.10.5.4. How to validate the total switch
Description
Select a contact output as DO1 and/or DO2 when the total value exceeds a setting.
Settable range: 0.000001 to 99999999
Contact action:
ACTIVE ON : DO1/DO2: Normally off
ACTIVE OFF : DO1/DO2: Normally on
Note) Different values can be assigned to DO1 and DO2.
For actual keying, refer to the typical operation indicated below. Set the protection to OFF
beforehand. (See Section 4.4.1.)
Operation
(example)
Set the DO1 output to “TOTAL SWITCH”, and change the setting value from 10000[m
3
] to 100[m
3
].
Also, set the contact to “ACTIVE ON”.
Key operation Description Display
Press the key twice to display “OUTPUT SETUP”.
OUTPUT SETUP
ENT
Press the
ENT
key once to display “ZERO ADJUSTMENT”.
ZERO ADJUSTMENT
SET ZERO
Press the key for 6 times to display “DO1 OUT”.
* Press the
key again to display “DO2 OUT”.
DO1 OUT
NOT USED
ENT
Press the
ENT
key once to blink the cursor.
DO1 OUT
NOT USED
Press the key for 6 times to display “TOTAL SWITCH” on the 2nd
line.
DO1 OUT
TOTAL SWITCH
ENT
Press the
ENT
key once to display the setting screen of “TOTAL
SWITCH”.
TOTAL SWITCH
10000 m3
ENT
Press the
ENT
key once to blink the cursor.
TOTAL SWITCH
00010000 m3
Press the key for 3 times to move the cursor.
TOTAL SWITCH
00010000 m3
Press the key for 10 times to set “0”.
TOTAL SWITCH
00000000 m3
Press the key twice to move the cursor.
TOTAL SWITCH
00000000 m3
Press the key once to set “1”.
TOTAL SWITCH
00000100 m3
ENT
Press the
ENT
key once to register.
TOTAL SWITCH

COMPLETE

――― “TOTAL SWITCH” has been registered. ―――
STATUS OUT
CONTACT ACTION
ENT
Press the
ENT
key once to display “CONTACT ACTION”.
CONTACT ACTION
ACTIVE ON
ENT
Press the
ENT
key once to register “ACTIVE ON”(normally off).
* To select normally on, press the
key.
CONTACT ACTION

COMPLETE

――― “ACTIVE ON” has been registered. ―――
STATUS OUT
CONTACT ACTION
ESC
Press the
ESC
key twice and then press the key for 3 times to enter
the measurement mode.
0.000 %
0.000 m
3
Time
Setting value
Total value
ON or OFF