-10-
3.3.4. Wiring to each terminal
3.3.4.1. Flow transmitter : FSV···S (IP66)
Carry out wiring to each terminal according to the following figure.
SG A
-
B
+
123
RS-485
L N FG
123
+
-
FG
123
+
--
+
DO1 DO2
+
-
I out
GND
HF1 HF2
GND
123456 7 8 910
TO SENSOR
SHSH
DOWN STRUP STR
TROUT
DC30V, 50mA
-
+
Power cable
Downstream
sensor cable
Upstream
sensor cable
Output signal cable
(analog output, DO1,
DO2, Communication)
External ground terminal
Main board terminal block
Ground terminal (M4)
Iout : Analog output
DO1, 2 : Transistor/open
collector
To upstream
sensor
White
To downstream
sensor
Black
White
Black
Yellow
AC power supply
100 to 120V AC
or 200 to 240V AC
50/60Hz
DC power supply
20 to 30V DC
Communication board terminal
block (option)
Power supply board terminal block
Note 1) Terminal block is insertion type to connect a cable. Use bar terminal as crimp-style terminals.
Note 2) Be sure to connect ground terminal to external ground terminal. (Class D grounding)
Note 3) For output signal, use multiple core cable as required.
Note 4) Differential signal line of RS-485 consists of two pins.
means B+, and means A-.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fuji Electric Time Delta-C FSV-2 and is the answer not in the manual?

Fuji Electric Time Delta-C FSV-2 Specifications

General IconGeneral
BrandFuji Electric
ModelTime Delta-C FSV-2
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals