EasyManua.ls Logo

Fuji Electric Time Delta-C FSV-2 - Insulation Resistance Measurement

Fuji Electric Time Delta-C FSV-2
119 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-81-
6.2.3. How to measure the insulation resistance
6.2.3.1. Flow transmitter : FSV···S (IP66)
Turn off power before opening the flow transmitter cover.
The power terminals are provided with an arrester as standard.
Measurement point: measure between power terminal and ground terminal, each outputs and ground terminal.
The insulation resistance performance of the equipment is 100 M/500 V DC.
L N
GNDGND
L N FG
123
+
-
FG
123
AC power supply
DC power supply
Power supply board terminal block
CAUTION