-33-
4.9. Output Setting
4.9.1. Setting of flow rate range
4.9.1.1. Setting of flow rate range (single range)
Description
The range (full scale) of flow rate to be measured is set.
* The analog output (4-20mA) corresponds to the range setting.
Settable range: 0.3 to 32 [m/s] in terms of flow velocity in piping
* The piping parameters and FLOW UNIT must be set beforehand.
* If a value beyond the settable range is inputted, "INPUT ERROR" appears and then last
setting is resumed.
* If "piping parameters" or "FLOW UNIT" has been changed after setting the range,
recommence the range setting.
<Note> The flow rate unit is as selected by "FLOW UNIT" in the "MEASURE SETUP" mode.
(Refer to Section 4.8.2.)
・
Setting range of the full scale frow rate
<Note>
Converted flow rate in the Table 1 is the calculation results obtained
by using the internal diameters of pipes in the left columns.
Perform calculation using the actual internal diameters for accuracy.
Simple formula for calculation of flow verocity
For actual keying, refer to the typical operation indicated below. Set the protection to OFF beforehand. (See Section 4.4.1.)
Operation
(example)
Set the range type to single range and “FULL SCALE1” to flow rate 60m3/h.
* Set the piping parameters and "FLOW UNIT" beforehand.
Key operation Description Display
▼
Press the key twice to display “OUTPUT SETUP”.
OUTPUT SETUP
ENT
▼
Press the
ENT
key to enter the “ZERO ADJUSTMENT” mode.
ZERO ADJUSTMENT
SET ZERO
▼
Press the key for 4 times to display “RANGE”.
RANGE
ENT
▼
▼
Press the
ENT
key once to display “KIND”.
Because flow rate (factory set) is already registered, go to the next step
Press the
key to display
“RANGE TYPE”
Because single range (factory set) is already registered, go to the next
step.
KIND
FLOW RATE
RANGE TYPE
SINGLE
▼
Press the key once to display “FULL SCALE1”.
FULL SCALE1
15.000 m3/h
ENT
▼
Press the
ENT
key once to blink the cursor.
FULL SCALE1
00015.000 m3/h
▼
▼
▼
▼
Move the cursor by the key, and change the numeric value by the
key.
00015.000 m3/h
00065.000 m3/h
00065.000 m3/h
▼
▼
▼
▼
Change the full scale1 to “60”.
Note) To change the decimal point position, align the cursor with a place
to change to and press the
key likewise.
FULL SCALE1
0000060.0 m3/h
ENT
▼
▼
▼
▼
Press the
ENT
key once to register.
FULL SCALE1
COMPLETE
↓
――― FULL SCALE1 has been registered. ―――
FULL SCALE1
60.000 m3/h
20mA
4mA
0 100%
Flow rate
Full scale 1
Flow velocity range: 0.3
~
32 [m/s] <Table1>
Int. dia.
of pipes
[mm]
25 0.530 to 56.5 8.84 to 942
50 2.12 to 226 35.3 to 3770
80 5.43 to 579 90.5 to 9651
100 8.48 to 905 141 to 15080
150 19.1 to 2036 318 to 33929
200 33.9 to 3619 565 to 60319
300 76.3 to 8143 1272 to 135717
Flow rate unit
[ m
3
/h ]
[ L/min ]