CHAPTER 3
Small Configuration
Installing the 19-Inch (FC9682HSW3) Heat Baffle
FNC-7500-0061-200
Issue 1, May 2009
FLASHWAVE 7500 Release 6.1
Equipment Installation
3-50
Fujitsu and Fujitsu Customer Use Only
3 Identify the left and right shelf flanges. See Figure 3-31 [p. 3-48] or Figure 3-32 [p. 3-49] and
Figure 3-33 [p. 3-50].
Note: At first glance the two flanges appear to be identical, but they are not. As shown in Figure 3-33
[p. 3-50] for 19-inch rack mounting, the four clearance holes on the side of each flange are closer to
the bottom of the flange than to the top. The flanges for 23-inch rack mounting are similar.
4 Is the heat baffle to be installed in a 19-inch relay rack?
If YES:
Proceed to Step 5 [p. 3-50].
If NO:
Proceed to Step 8 [p. 3-51].
5 Identify the flange mounting holes for 19-inch rack installation on the side of the heat baffle.
See Figure 3-34 [p. 3-50].
6 Using four pan-head Phillips M4 screws (8 mm long) on each side, secure the left and right
shelf flanges to the heat baffle as shown in Figure 3-31 [p. 3-48].
Left Shelf Flange Right Shelf Flange
Figure 3-33: 19-Inch Heat Baffle Mounting Flanges (Front and Side Views)
Figure 3-34: Flange Mounting Holes on Right Side of Heat Baffle (19-Inch Rack Installation)
Front
Mounting Holes
m1656tg_1