CHAPTER 4
ETSI Configuration
Installing Power and Ground Cables
4-69
FLASHWAVE 7500 Release 6.1
Equipment Installation
Fujitsu and Fujitsu Customer Use Only
FNC-7500-0061-200
Issue 1, May 2009
15 Locate the rack/shelf power harnesses (PC660-0105-T019 and PC660-0105-T020,
Figure 4-44 [p. 4-63]) for the shelf.
Note: The length of the cables may be altered at the discretion of the installer to ensure proper
length.
16 Prepare the power leads by installing the terminal lugs that are required on one end of the
cable (see Figure 4-44 [p. 4-63]). Ensure that no wire strands are shorting terminals together
and that leads are securely fastened. The cable should now have terminal lugs on both ends of
the power cable.
Note: The shelf power wiring is the same with all rack configurations. Observe the color coding of the
power cable.
17 On the SIA of the shelf identified in Step 14 [p. 4-68], remove the plastic covers on the shelf
power terminal strips located on the bottom left and bottom right of the SIA (see Figure 4-47
[p. 4-65]).
18 Connect both ends of cable GA of the power harness as follows:
a. Identify lug GA in the power harness (see Figure 4-44 [p. 4-63]) and connect it to shelf
terminal GA (see Figure 4-47 [p. 4-65]).
b. Connect the other end of the same cable to PDP terminal A2-1 +RTN (see Figure 4-45
[p. 4-64]).
19 Connect both ends of cable GB of the power harness as follows:
a. Identify lug GB in the power harness (see Figure 4-44 [p. 4-63]) and connect it to shelf
terminal GB (see Figure 4-47 [p. 4-65]).
b. Connect the other end of the same cable to PDP terminal B2-1 +RTN (see Figure 4-45
[p. 4-64]).
20 Connect both ends of cable MA of the power harness as follows:
a. Identify lug MA in the power harness (see Figure 4-44 [p. 4-63]) and connect it to shelf
terminal MAIN A (see Figure 4-47 [p. 4-65]).
b. Connect the other end of the same cable to PDP terminal A2-1 -BATT (see Figure 4-45
[p. 4-64]).
Revision 1, June 2009