CHAPTER 6
Installing/Removing Modules, Filler Panels and Plug-In Units
Installing/Removing XFP Modules in a 4:1 10G Muxponder Unit
6-23
FLASHWAVE 7500 Release 6.1
Equipment Installation
Fujitsu and Fujitsu Customer Use Only
FNC-7500-0061-200
Issue 1, May 2009
3 If necessary, record the serial number and issue number of the XFP module being installed.
4 Install the module into the proper slot of the muxponder plug-in unit.
5 Will fibers be connected to the XFP module at this time?
If YES:
Continue with Step 6 [p. 6-23].
If NO:
Go to Step 8 [p. 6-23].
6 Clean the optical connectors. Refer to Fiber Cable Handling.
7 Connect the fiber-optic cables to the XFP module.
8 Close the stainless steel client connection drawer (see Figure 6-8 [p. 6-14]), and gently tighten
the two thumb screws that secure it on the front of the muxponder plug-in unit.
This procedure is complete.