INSTALLATION
51
PULSE Installaon, Commissioning and Servicing Manual - Revision 19
7.7 LPG Trade Measurement Verification Process - Version 1.20
Enter Service Mode
1. Go to LPG MENU – press FILL.
2. Go to LPG TEST - press 4 or 6 to select fuelpoint to be tested, press 5 to turn Test
Mode to ON.
3. Hold C to exit Service Mode and enter Test Mode.
4. Do a test delivery (Do not open the nozzle until after the pressurisation bars have
gone).
Litres display:
Shows the corrected volume
Dollars display:
Shows the uncompensated volume
When in Test Mode:
LPG price window: ‘VCF’ (volume correction factor to 3 decimal places)
‘D15’ (density corrected to 15°C, to 3 decimal places)
‘T’ (liquid temperature, to 1 decimal place)
5. Press FILL to leave test mode.
Note: Non-LPG hose will be disabled in Test Mode.