ZP3 Fire Control Panel Installation, Commissioning and Maintenance Manual
Page 122 REV 11 (ISS 08/03/2010)
Table 32: Device definition table and device type analogues interpretation
Model Description Code Reading 1 Reading 2 Reading 3
ZP710-2 Analogue ionization sensor 212 197-226 (213) 228-255 (245) 197-226 (213)
ZP720-2 Analogue heat sensor 213 197-226 (213) 228-255 (245) 165-194 (180)
ZP720-3 Analogue heat sesnor 217 197-226 (213) 228-255 (245) 039-068 (054)
ZP725-2 Analogue heat sensor –with rate of rise
element
214 197-226 (213) 228-255 (245) 133-162 (152)
ZP730-2 Analogue optical sensor 215 197-226 (213) 228-255 (245) 102-131 (118)
ZP732-2 Analogue duet sensor (optical/heat) 216 197-226 (213) 228-255 (245) 070-100 (084)
ZP5-IF8-22 8 way interface fire callpoint board 222 197-226 (213) 197-226 (213) 197-226 (213)
ZP5-IF8-23 8 way interface fire sprinkler board 223 197-226 (213) 197-226 (213) 165-194 (180)
ZP740-2-23 Analogue interface fire sprinkler 223 197-226 (213) 197-226 (213) 165-194 (180)
ZP5-IF8-24 8 way interface fire general purpose
board
224 197-226 (213) 197-226 (213) 133-162 (152)
ZP740-2-24 Analogue interface fire general purpose 224 197-226 (213) 197-226 (213) 133-162 (152)
ZP745 Interface unit 224 197-226 (213) 197-226 (213) 133-162 (152)
A45E Interface unit 224 197-226 (213) 197-226 (213) 133-162 (152)
ZP740ST Analogue interface for high sensitive
smoke detector (stratos)
233 197-226 (213) 165-194 (180) 165-194 (180)
ZLS1APIC Analogue interface for high sensitive
smoke detector (stratos)
233 197-226 (213) 165-194 (180) 165-194 (180)
ZP755 Loop sounder (all variants) 241 197-226 (213) 133-162 (152) 228-255 (245)
ZP750-2 Line relay 242 197-226 (213) 133-162 (152) 197-226 (213)
A50E Line relay 242 197-226 (213) 133-162 (152) 197-226 (213)
A51E High voltage line relay 242 197-226 (213) 133-162 (152) 197-226 (213)
ZP752-2 Dual line sounder unit 245 197-226 (213) 133-162 (152) 102-131 (118)
ZP753-2 Addressable LED indicator 246 197-226 (213) 133-162 (152) 070-100 (084)
ZP754*-2 Addressable line sounder 247 197-226 (213) 133-162 (152) 039-068 (054)
ZP755 Loop sounder (ZP754 mode) 247 197-226 (213) 133-162 (152) 039-068 (054)
ZP5-IF8-52 8 way interface fire non-fire/auxiliary
board
252 197-226 (213) 102-131 (118) 197-226 (213)
ZP740-2-52 Analogue interface non-fire/auxiliary 252 197-226 (213) 102-131 (118) 197-226 (213)
ZP5-IF8-53 8 way interface fire non-alarm/control
board
253 197-226 (213) 102-131 (118) 165-194 (180)
ZP740-2-53 Analogue interface non-alarm/control 253 197-226 (213) 102-131 (118) 165-194 (180)
ZP5-IF8-54 8 way interface fire non-alarm/control
board
254 197-226 (213) 102-131 (118) 133-162 (152)
ZP740-2-54 Analogue interface non-alarm/control 254 197-226 (213) 102-131 (118) 133-162 (152)
ZP5-IF8-62 8 way interface fire security latching
board
262 197-226 (213) 070-100 (084) 197-226 (213)
ZP740-2-62 Analogue interface security latching 262 197-226 (213) 070-100 (084) 197-226 (213)
ZP5-IF8-64 8 way interface fire security non-
latching board
264 197-226 (213) 070-100 (084) 133-162 (152)