GE Druck DPI 620-IS - Communicator Attached to a Network

GE Druck DPI 620-IS
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[EN] English - K0460 HART
®
device operations 8-9
Issue 1
Turn on the internal HART
®
resistor. This can be selected by
pressing icon.
6. Complete the electrical connections and continue with the
HART
®
menu operation.
8.3.3 Communicator
attached to a
network
In this example, the calibrator connects directly to a network.
There must be a 250Ω resistor in series with the loop power supply
and the HART
®
device.
1. Set the function for HART
®
:
No functions
on channel 2 (CH2)
HART
®
Function is set
250Ω resistor is set to Off
d
c
Home display
a
b
1
TAP
Set HART
®
User Manual Section 2.8.4