Miscellaneous Alarms
(Batteries must be connected)
Distribution Alarms
Step Action
1
Manually connect a piece of wire from the circuit breaker feed bus to the distribution alarm strip.
2
Verify an FAJ – Fuse Alarm Major is reported by the controller.
Remove the wire. Verify the alarm clears.
Repeat test for each distribution panel or sub-system.
ac Fail Alarms
26
Step Action
Turn off AC circuit breaker feeding a single rectifier.
27
Verify ACF – AC Fail Minor is reported for the correct rectifier ID.
Restore input and verify alarms clear and the controller returns to Normal.
4
Remove input from two or more rectifiers.
5
Verify MACF – Multiple AC Fail Major is reported for the correct rectifier IDs.
6
Turn on input circuit breaker turned off in Step 1 and verify alarms clear and the controller returns to
Normal.
Battery On Discharge Alarms
28
Step Action
1
Change BD alarm to 2 volts below float voltage (Menu > Configuration > Float Settings > Voltage Alarms >
BD).
Adjust the load to 50 amperes.
Verify the BD alarm occurs when the system voltage decreases to BD threshold.
Verify the BD alarm clears once the voltage has exceeded 0.5V above the BD alarm threshold.
5
Restore the BD alarm threshold to its previous setting.
High Voltage Alarms
Step Action
Confirm the HV alarm threshold (Menu > Configuration > Float Settings > Voltage Alarms > High Minor).
2
Adjust the float voltage to a value greater than this threshold
(Menu > Configuration > Float Settings > Set Point).
Verify an HV alarm is reported by the controller.
Restore the float voltage back to its original setting.
5
Restore the HV setting back to its original setting.
6
Verify the alarms clear and the controller returns to Normal.
26
Rectifier Input Fail Controller Alarms: is displayed and labeled “ACF” and “MACF”.
Input Fail Rectifier LED: non-Eco rectifiers LED is labeled “ACF”. Eco rectifiers LED is labeled “INF” (INput Fail).
27
DC fed Eco rectifiers do not report a failure (INF) when DC input is removed.
28
Eco systems do not alarm for battery discharges and may have BD thresholds settings different than non-Eco systems.