NE-M Installation Guide H5692448
850050111 Issue 03 August 2017 70
Manual Contactor Control and Alarms
29
Step Action
1
Open the contactor by controller command (Menu > Control / Operations > Disconnects).
2
Verify the controller reports a Contactor Open alarm.
30
3
Close the contactor by controller command.
4
Verify the alarms clear and the controller returns to Normal.
29
Skip if contactors are not present.
30
Contactor Open Alarm may be delayed by imminent LVD Alarm delay if enabled and configured.