30 GE INFORMATION D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
CHAPTER 1: BEFORE YOU START
Enclosure electro-
magnetic capability
Environmental
Physical
Enclosure Immunity As per:
IEEE C37.90.2
IEEE C37.90.3
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-8
Radiated Emissions CISPR 11 Class A
Ambient Temperature
Range
Operating:
40 °C to +75 °C (IEC 60068-2-1 and 2)
Note: D20E-K and D20E-C: +75 °C IEC 61010-1 rating
Storage:
40 °C to +85 °C (IEC 60068-2-1 and 2)
Humidity <95% Relative Humidity, non-condensing at +40 °C, 96 hrs. (IEC 60068-2-
78)
Altitude 2000 m (maximum)
Pollution Degree: II
Overvoltage Category: II
Ingress Protection: IP30 Front
Insulation Class: 1
Enclosure Protection
Rating
IP30-top, IP20-bottom (IEC 60529)
Vibration, Shock, Drop As per:
IEC 60068-2-6
IEC 60068-2-27
IEC 60068-2-31
Form 3U, Rack/Wall-mount
Dimensions 19.0 x 5.2 x 1.6 inches; 483 x 132 x 41mm
Weight 4.8 lbs; 2.2 kg (except D20E-K: 5.7 lbs or 2.6 kg)
Termination Facilities Compression Terminal Block: 2.5 mm
2
(#13 AWG) maximum