MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
Chapter 6 Parameter • 126 ARTDrive V2 series - Instruction Manual
Fast stop Usage of this command is optional. This command is used when the drive
is operated with Ramp and speed regulation. When the command is
active, the Ramp input reference is zeroed and the ramp operates on a
specific deceleration slope that can be set independently from the
standard deceleration slope. The command can be accessed either from a
communication source or a programmable digital input terminal.
NOTE! when Fast stop command is negated, the drive will restart unless also Start/Stop
command has been negated. The exception is when En/Disable control
parameter is programmed as "Stop/Fs&Spd=0". In this case the Start command
must be recycled after Fast stop is no more active in order to let the drive to start
again.
Jog This command provides momentary rotation of the drive with ramp and
speed reference settings independent of the ones defined for operation
with Start/Stop command.
NOTE! Start/Stop command takes priority over the Jog command. The Jog command can
be activated by concurrent sources: the [+/Jog] key on the keyboard, and a
boolean source that can be either a communication or application card or a
programmable digital input. The Jog command is complemented by a toggle
command for rotation direction inversion. The source of inversion may also be a
dedicated key on the keyboard/display module or a configurable source, both
sources may be concurrently active.
NOTE! Due to the double function of the keys, it is initially necessary to hit [Shift] and
[+/Jog] in order to turn the keyboard section into jog mode.
After that, the simple pressure of [+/Jog] key will cause the drive to jog, and the
pressure of the [-/<->] key will cause inversion of the rotation. To exit keyboard jog
mode press [</Escape].
Figure C00 note:
I O KEYS - DI0 & TermStrStp src are required=1 to run
DIGITAL EDGE - Terminals src inputs are level sensitive run interlocks
DIGITAL LEVEL - All signals are level triggered, terminals are run interlocks
(1) EGDE SELECTION - Inputs are processed with Edge sensitive logic
LEVEL SELECTION - Inputs are processed with Level sensitive logic
(2) Emergency Stop with alarm Emg Stp at Speed 0