ARTDrive V2 series - Instruction Manual Chapter 4 Wiring Procedure • 59
NOTE! The technical data of the fuses, e.g. dimensions, weights, heat dissipation,
auxiliary contactors, are reported in the corresponding data sheets.
NOTE! Use specified fuse or CSA certified equivalent
4.6.2 External Fuses of the Power Section DC Input Side
Use the following fuses when the drive is powered from a common DC bus.
Table 4.6.2.1: External Fuses Type for DC Input Side
Fuses type code code
1007 Z14GR6 F4M01 A70P10 FWP10A14F S7G49
1015
1022
1030
2040
2055 Z14GR20 F4M07 A70P20-1 FWP20A14F S7G48
2075 Z14GR32 F4M11 A70P30-1 FWP30A14F S7I50
3110 Z14GR40 F4M13 A70P40-4 FWP40B S7G52
3150 Z22GR63 F4M17 A70P60-4 FWP60B S7I34
4220
S00C+üF1/80/80A/660V F4EAF A70P80 FWP80 S7G54
4300
S00C+üF1/80/100A/660V F4EAG A70P100 FWP100 S7G55
4370
S00C+üF1/80/125A/660V F4EAJ A70P150 FWP150 S7G56
5450
S00C+üF1/80/160A/660V F4EAL A70P175 FWP175 S7G57
5550
S00üF1/80/200A/660V F4G23 A70P200 FWP200 S7G58
6750
S1üF1/110/250A/660V F4G28 A70P250 FWP250 S7G59
7900
S1üF1/110/315A/660V F4G30 A70P350 FWP350 S7G61
71100
S1üF1/110/400A/660V F4G34 A70P400 FWP400 S7G62
71320
S1üF1/110/500A/660V F4E30 A70P500 FWP500 S7G63
81600
S1üF1/110/500A/660V F4E30 A70P500 FWP500 S7G63
Fuses type code code
2002
-
A100P15
-
S85A0
2003
-
A100P15
-
S85A0
2005
-
A100P20
-
S85A1
3007
-
A100P30
-
S85A2
3010
-
A100P35 FWJ35 S85A3
3015
-
A100P50 FWJ50 S85A4
3020
-
A100P60 FWJ60 S85A5
4025
-
A100P60 FWJ60 S85A5
4030
-
A100P70 FWJ70 S85A6
4040
-
A100P80 FWJ80 S85A7
4050
-
A100P100 FWJ100 S85A8
5060
-
A100P125 FWJ125 S85A9
5075
-
A100P150 FWJ150 S85B0
7100
-
A100P200 FWJ200
S85B1
7125
-
A100P250 FWJ250
S85B2
7150
-
A100P250 FWJ250
S85B2
8200
-
A100P400 FWJ400
S85B4
avy0701
FWP20A14FF4M05
Drive type
Europe America
Z14GR10 S7G49A70P10 FWP10A14FF4M03
AVy…-5 (575V)
Fuses type
Fuses type
AVy…-4 (230V…480V)
Europe America
Drive type
S7G48Z14GR16 A70P20-1
Fuse manufacturers: Type Z14..., Z22,
S00 ..., S1..., S2... Jean Müller, Eltville
A70P... Gould Shawmut
FWP... Bussmann
NOTE! The technical data of the fuses, e.g. dimensions, weights, heat dissipation,
auxiliary contactors, are reported in the corresponding data sheets.
NOTE! If external units are connected to the terminals of the DC Link circuit, then
separate semiconductor fuses (DC) must be used for each external unit and
they must be sized to protect each external unit.