30 • Chapter 3 Installation Guidelines ARTDrive V2 series - Instruction Manual
3.2 Watts Loss, Heat Dissipation, Internal Fans and Minimum Cabinet
Opening Suggested for Cooling
The heat dissipation of the Drives depends on the operating state of the connected
motor. The table below shows values that refer to operation at default switching
frequency (see section 2.3.4, “AC Output”), Tamb 40°C, typ. motor power
factor and nominal continuous current.
Table 3.2.1: Heat Dissipation and Required Air Flow
AVy…-4
(230…480Vac) @U
LN
=230Vac @U
LN
=400Vac @U
LN
=460Vac Internal fan Heatsink fans
[W] [W] [W]
[m
3
/h] [m
3
/h]
1007 38 48.2 45.0 11 -
1015 62 77.5 72.0 11 30
1022 83 104.0 96.3 11 30
1030 110 138.3 126.7 11 30
2040 144 179.5 164.1 11 2x30
2055 184 233.6 215.6 11 2x30
2075 264 327.4 300.8 11 2x30
3110 304 373 340 30 2x79
3150 416 512 468 30 2x79
4220 526 658 582 80
4300 691 864 780 170
4370 880 1100 1000 170
5450 1000 1250 1100 340
5550 1264 1580 1390 340
6750 1560 1950 1750 650
7900 1952 2440 2200 975
71100 2280 2850 2560 975
71320 2720 3400 3050 975
81600 N.A. 4400 3950 1820
AVy…-5
(575Vac) Internal fan Heatsink fans
[m
3
/h] [m
3
/h]
2002 11 30
2003 11 30
2005 11 2x30
3007 30 2x79
3010 30 2x79
3015 30 2x79
3020 30 2x79
4025 2x80
4030 2x80
4040 170
5050 340
5060 340
5075 340
6100 650
7125 975
7150 975
8200 975
avy3110
2760
2760
Airflow of fan
75
80
128
[W]
215
266
Airflow of fan
Heat Dissipation
Heat Dissipation
U
LN
= 575Vac
3250
338
453
1155
1480
515
620
810
1070
2150
NOTE!
• f
SW
=default; I
2
=I
2N
All AVy drives have internal fans.
• Heat dissipation losses refer to default switching frequency.