Chapter 7 Appendix • 318 ARTDrive V2 series - Instruction Manual
CH1
0.1V
1mS
CH1
0.1V
1mS
Figure 7.1.1: Output Current (Reaction Time @ 2ms) Displaying
CH1
0.1V
1mS
CH1
0.1V
1mS
Figure 7.1.2: Optimal Output Current (Reaction Time @ 1ms) Displaying
7.2 Manual Tuning of the Flux Regulator
This tuning is necessary only with applications where the use of the
field weakening is required.
Use a 2 channel digital scope.
In the INTERFACE / An Out 1 and INTERFACE / An Out 2 menues set the
analog outputs 1 & 2 (see chapter 6.1.1 how to connect the variables):
- C08.00 - AO 1 src sorce connect the Flux ref variable
- C09.00 - AO 2 src source connect the Flux variable.
On 21-22 terminals (see chapter 4.3) place channel 1 of the digital scope
(CH1) on the Flux ref (flux reference) signal; on 23-22 terminals place
channel 2 (CH2) for the Flux signal (actual flux).