ARTDrive V2 series - Instruction Manual Chapter 8 Appendix • 349
[5] 5.5kW - 7.5Hp [7] 575V - 15Hp
[6] 7.5kW - 10Hp [8] 575V - 20Hp
[7] 11kW - 15Hp [9] 575V - 25Hp
[8] 15kW - 20Hp [10] 575V - 30Hp
[9] 22kW - 25Hp [11] 575V - 40Hp
[10] 30kW - 30Hp [12] 575V - 50Hp
[11] 37kW - 40Hp [13] 575V - 60Hp
[12] 45kW - 50Hp [14] 575V - 75Hp
[13] 55kW - 60Hp [16] 575V - 100Hp
[14] 75kW - 75Hp [17] 575V - 125Hp
[15] 90kW - 100Hp [18] 575V - 150Hp
[16] 110kW- 125Hp
[17] 132kW- 150Hp
[18] 160kW- 200Hp
[19] 250kW- 300Hp
[20] 315kW- 450Hp
[21] 500kW- 600Hp
[22] 160kW-200Hp
[23] 400kW- 500Hp
8.2.2 Database Errors (DB Errors)
DB errors are caused by a incorrect setting in a single parameter. This problem
is originated in the database calculation. For example the most common are:
- DB error Limit HIGH
- DB error Limit LOW
The message DB error is displayed by the drive in this format:
DB err IPA: error code
The IPA denotes the parameter number which caused the DB error calculation.
The error code denotes the type error.
Example of message DB error displayed:
DB ERR 3420: 5
This means that the DB error is caused by IPA 3420 (B0F.00 - V/f voltage)
which is below the low limit; Error code 5 denotes the type error (for the DB error
code values list see below). To find the low limit, which depends on drive
configuration, it is possible to go to the V/f voltage parameter on the keypad.
Press the [Shift] key and then the [Help] key, the following will be displayed:
Max Value
min Value
Def(ault) Value
unit
raw value
IPA
Description
(Access) mode