58 • Chapter 4 Wiring Procedure ARTDrive V2 series - Instruction Manual
4.6 Circuit Protection
4.6.1 External Fuses of the Power Section
The inverter must be fused on the AC Input side. Fuses, using Semiconductor
grade fuses as per table 4.6.1.1. Use fast fuses only.
Connections with three-phase inductance on AC input will improve the DC link
capacitors life time.
Table 4.6.1.1: External Fuse Types for AC Input Side
Europe
1007
1015
1022 25000
1030 10000
2040 25000 GRD2/20 (F4D15) or Z14GR20 (F4M07) A70P20 FWP20 (S7G48)
2055 25000 GRD2/25 (F4D16) or Z14GR25 (F4M09) A70P25 FWP25 (S7G51)
2075 10000 GRD3/35 (F4D20) or Z22GR40 A70P35 FWP35 (S7G86)
3110 25000 GRD3/50 (F4D21) or Z22GR40 A70P40 FWP40 (S7G52)
3150 10000 GRD3/50 (F4D21) or Z22GR50 (F4M15) A70P40 FWP40 (S7G52)
4220 71320 10000
1007 50000
1015 50000
1022 50000 A70P10 FWP10 (S7G49)
1030 50000
2040 50000
2055 50000 GRD2/20 (F4D15) or Z14GR20 (F4M07) A70P20 FWP20 (S7G48)
2075 50000 GRD2/25 (F4D16) or Z14GR25 (F4M09) A70P25 FWP25 (S7G51)
3110 50000 GRD3/50 (F4D21) or Z22GR40 A70P35 FWP35 (S7G86)
3150 50000 GRD3/50 (F4D21) or Z22GR50 (F4M15) A70P40 FWP40 (S7G52)
4220 25000 GRD3/50 (F4D21) or Z22GR50 A70P50 FWP50 (S7G53)
4300 25000 S00C+üf1/80/80A/660V (F4EAF) or Z22gR80 A70P80 FWP80 (S7G54)
4370 25000 S00C+üf1/80/100A/660V (F4EAG) or M00üf01/100A/660V A70P100 FWP100 (S7G55)
5450 25000
5550 25000
6750 25000
7900 25000
71100 25000
71320 25000
81600 25000
2002 25000 (*)
2003 25000 (*)
2005 25000 (*) GRD2-16 (F4D14) A70P15 FWP15
(S848B)
3007 25000 (*) GRD2/25 (F4D16) or Z14GR25 (F4M09) A70P25 FWP25
(S7G51)
3010 25000 (*) Z14GR32 (F4M11) A70P30-1 FWP30A14F
(S7I50)
3015 25000 (*) GRD3/50 (F4D21) o Z22GR54 (F4M13) A70P40 FWP40
(S7G52)
3020 25000 (*)
4025 50000
4030 50000
4040 50000 Z22GR63 (F4M17) A70P60-4 FWP60B
(S7I34)
5050 50000 S00C+üf1/80/80A/660V (F4EAF) or Z22gR80 A70P80 FWP80
(S7G54)
5060 50000 S00C+üf1/80/100A/660V (F4EAG) or M00üf01/100A/660V A70P100 FWP100 (S7G55)
5075 50000 S00C+üf1/80/125A/660V (F4EAJ) or M00üf01/125A/660V A70P125 FWP125 (S849B)
6100 50000 S00C+üf1/80/160A/660V (F4EAL) or M00üf01/160A/660V A70P150 (S7G56)
7125 50000 S1üf1/110/250A/660V or M1üf1/250A/660V (F4G28) A70P200 FWP200 (S7G58)
7150 50000 S1üf1/110/250A/660V or M1üf1/250A/660V (F4G28) A70P250 FWP250 (S7G59)
8200 50000 S2üf1/110/400A/660V or M2üf1/400A/660V (F4G34) A70P400 FWP400 (S7G62)
avy0700
(*) 50000 [h] only with input choke
FWP400
FWP175 (S7G57)
(S7G62)
FWP300 (S7G60)
FWP10A14F
A70P50 FWP50 (S7G53)
(S7G49)A70P10
Drive type
F1 - Fuses type (code)
DC link capacitors life time
[h]
A70P20 FWP20
A70P10
Connections without three-phase reactor on AC input
America
(S7G49)
(S7G48)
FWP10
GRD2/16 (F4D14) or Z14GR16 (F4M05)
A70P10 FWP10
GRD2/10 (F4D13) or Z14GR10 (F4M03)
FWP20
GRD2/10 (F4D13) or Z14GR10 (F4M03)
Connections with three-phase reactor on AC input
A70P20
For these types an external reactor is mandatory if the AC input impedence is equal or less than 1%
A70P400
A70P175
25000
AVy…-4 (230V…480V)
GRD2/16 (F4D14) or Z14GR16 (F4M05)
A70P300
AVy…-5 (575V)
S2üf1/110/400A/660V or M2üf1/400A/660V (F4G34)
S1üf1/110/250A/660V or M1üf1/250A/660V (F4G28)
GRD2/10 (F4D13) or Z14GR10 (F4M03)
GRD3/50 (F4D21) or Z22GR50 (F4M15)
S00C+üf1/80/160A/660V or M00üf01/160A/660V (F4EAL)
Connections with and/or without three-phase reactor on AC input
(S7G48)
(S7G49)
Fuse manufacturers:
Type Type GRD2... (E27), GRD3... (E33),
M... (blade fuses), Z14... 14 x 51 mm,
Z22... 22 x 58 mm, S.... Jean Müller, Eltville
A70... Gould Shawmut
FWP... Bussmann