78 • Chapter 5 Quick Start Up Guide ARTDrive V2 series - Instruction Manual
of operation and dozens of combinations of configurations, this guide will cover
most applications that are not being started up by a service engineer.
The instruction book can be used to make more complex changes to standard
configuration beyond this set up.
Standard Wiring scheme: see chapter 4, Wiring Procedure.
5.3 Pre-power Checks
The following should be checked before switching the Drive ON :
Grounds / Grounding
- Verify ground connections drive to motor
- Verify AC Inputs, AC Outputs and control wiring are clear of grounds
- Drive power supply may be intentionally grounded
Connections
- Check AC Inputs (U1/L1, V1/L2, W1/L3), AC Outputs (U2/T1, V2/T2, W2/
T3) for tightness and good connections
- DC connection with an optional external Braking Unit (C,D)
- Motor thermistor (78,79)
- “Digital Output 0” Relay (80,82 n.o), “Digital Output 1” Relay (83,85 n.o)
- Regulation Board connections:
1………46 on connectors XS, XE
12 ENABLE Drive (close to active)
13 Digital input 1
16 Common for terminal board
18 + 24V Common
19 + 24VDC (internal)
- Any option board connections
Figure 5.3.1: Terminal connections
12 13 14 15 16 18 19
- Encoder connections (if used)
- Record Motor Name Plate Data, encoder infomation and mechanical data.
Motor Data
Table 5.3.1: Motor Data
HP (kW)
Amps
Volts
Hz
Rpm
Cos phi (power factor)
Tac h t ype
Tac h P PR
Motorrotation for machine fwd direction [CW/CCW]
Gearbox ratio