ARTDrive V2 series - Instruction Manual Chapter 5 Quick Start Up Guide • 89
5.6 Additional Information (Configuration of the OK Relay)
5.6.1 Analog Input Tuning
On the regulation card, the following configuration can be set:
-10V…+10V 0-20mA
0-10V 4-20 mA
Analog input 1 S8 = OFF S8 = ON
Analog input 2 S9 = OFF S9 = ON
Analog input 3 S10 = OFF S10 = ON
tab 561
ON Jumper OFF Jumper
Input signal
Analog inputs
NOTE! It is important to remember that the hardware configuration on the regulation
card has to be set according to the selected input.
- 10V… +10V
The input allows a maximum voltage of +/-10V.
The motor rotation direction is obtained according to the signal polarity. Input
voltage > 10V or >-10V cause saturation of the count value.
0–10V, 0–20mA
The input allows a maximum voltage of +10V or 0…20mA current signal. If
used as reference, the signal must be always positive sign. Through AI 1 sgn
src it is possible to change the motor rotation.
4 –20 mA
The input allows to connect 4… 20mA current signal.
If used as reference, the signal must be always positive sign. Through AI 1 sgn
src it is possible to change the motor rotation.
Through the An inp X <thr output it is possible to monitor the state of the input
current signal. If the current is lower than the value set in the An inp 1 thr
parameter, an output signal is supplied (error signal). This signal can also be
defined as digital output.
How to perform the self-tuning procedure of the Analog input 1, if the input is
- 10V… +10V (factory).
Tune Analog input 1 offset
C INTERFACE / C01 An Inp 1
Refer to 0 the position of the potentiometer connected to Analog input 1 terminals.
Enter the C01.18 - AI 1 offs tune parameter: "Start…" message will be displayed,
than press [Enter] key to run the procedure.
Wait up to "Autotune End" message will be displayed, than press three time
[Escape] key.