ARTDrive V2 series - Instruction Manual Chapter 2 Inspection Procedure,... • 19
2.3 Standard Specifications
2.3.1 Permissible Environmental Conditions
ENVIRONMENT
T
A
Ambient temperature [°C] ________ 0 … +40; +40…+50 with derating
T
A
Ambient temperature [°F] ________ 32 … +104; +104…+122 with derating
Installation location ______________ Pollution degree 2 or better (free from direct sunlight, vibration,
dust, corrosive or inflammable gases, fog, vapour oil and dripped
water, avoid saline environment)
Degree of protection ______________ IP20
IP54 for the cabinet with externally mounted heatsink for size
type 1007 to 3150 (230/480Vac series) and 2002 to 3020
(575Vac series)
Installation altitude _______________ Up to 2000 m (6560 feet) above sea level; over 1000 m (3280
feet) a current reduction of 1.2% for every 100 m (328 feet) of
additional height applies .
Temperature:
operation
1)
_________________________
0…40°C (32°…104°F)
operation
2)
_________________________
0…50°C (32°…122°F)
storage _________________ -25…+55°C (-13…+131°F), class 1K4 per EN50178
-20…+55°C (-4…+131°F), for devices with keypad
transport ________________ -25…+70°C (-13…+158°F), class 2K3 per EN50178
-20…+60°C (-4…+140°F), for devices with keypad
Air humidity:
operation ________________ 5 % to 85 %, 1 g/m
3
to 25 g/m
3
without moisture condensation
or icing (Class 3K3 as per EN50178)
storage _________________ 5% to 95 %, 1 g/m
3
to 29 g/m
3
(Class 1K3 as per EN50178)
transport ________________ 95 %
3)
, 60 g/m
3
4)
Air pressure:
operation ________________ [kPa] 86 to 106 (class 3K3 as per EN50178)
storage _________________ [kPa] 86 to 106 (class 1K4 as per EN50178)
transport ________________ [kPa] 70 to 106 (class 2K3 as per EN50178)
STANDARD
Climatic conditions _______________ IEC 68-2 Part 2 and 3
Clearance and creepage ___________ EN 50178, UL508C, UL840 degree of pollution 2
Vibration _______________________ IEC68-2 Part 6
EMC compatibility ________________ EN61800-3 (see “EMC Guidelines” instruction book)
Approvals ______________________ CE, UL, cUL, CSA (for AVy-...-5 series only).
1)
Parameter Ambient temp = 40°C (104°)
Ambient temp = 0 ... 40°C (32°...104°F)
Over 40°C: - current reduction of 2% of rated output current per K
- remove front plate (better than class 3K3 as per EN50178)
2)
Parameter Ambient temp = 50°C (122°F)
Ambient temp = 0 ... 50°C (32°...122°F)
Current derated to 0.8 rated ouput current
Over 40°C (104°): removal of the top cover (better than class 3K3 as per EN50178)
3)
Greatest relative air humidity occurs with the temperature @ 40°C (104°F) or if the
temperature of the device is brought suddenly from -25 ...+30°C (-13°...+86°F).
4)
Greatest absolute air humidity if the device is brought suddenly from 70...15°C (158°...59°F).