I FUNCTION
FUNCTION / DC braking
The Function allows to stop the motor with a direct current braking.
The current injection can be activated via an external command, via the I00.00 - DCbrake
cmd src source or automatically via an internal command when the stop command is
performed.
Such command can be activated by setting I00.10 - DCbrake mode = At stop.
It is possible to have simultaneously both the internal and the external command.
They both work on a OR logic. Furthermore, the function is made of:
- a waiting phase between the command emission and the duration of the
programmable injection
- a direct current injection phase, whose intensity and duration can be programmed
Via I00.11 - DCbrake delay it is possible to set the waiting phase between the command
and the injection duration.
NOTE! If the external command is a pulse shorter than the programmed injection time, the
injection phase lasts for the programmed time.
If the external command is a pulse longer than the programmed injection time, the
injection phase lasts till the end of the external command.
With I00.20 -DCBrake duration it is possible to set the current injection duration while
I00.21 -DCBrake current allows to set the current intensity.